In this case, set the same value for the PID Control instruction's output range and the TPO(685) instruc-
tion's manipulated variable range. For example, when the PID Control instruction's output range and the
TPO(685) instruction's manipulated variable range are both set to 12 bits (0000 to 0FFF hex), the duty
ratio is calculated by dividing the manipulated variable from the PID Control instruction by 0FFF hex
and TPO(685) converts that duty ratio to a time-proportional output.
External Wiring Example
Connect the Transistor Output Unit to a solid state relay (SSR) as shown in the following diagram.
Transistor Output Unit
12 to 24 VDC
COM

Parameter Settings

Control data
Item
Word
Bits
C
00 to 03
Manipulated
variable range
04 to 07
Input type
08 to 11
Input read tim-
ing
12 to 15
Output limit
control
C+1
00 to 15
Control period
C +2
00 to 15
Output lower
limit
C +3
00 to 15
Output upper
limit
C+4
00 to 15
Work area
C+5
00 to 15
C+6
00 to 15
Note When the output limit control function is enabled, set the lower and upper limits as follows:
0000 hex ≤ lower limit ≤ upper limit ≤ 2710 hex.
Execution
• The instruction is executed while the input condition is ON.
• When instruction execution starts, the output bit (R) is turned ON/OFF according to the duty ratio.
CP1E CPU Unit Instructions Reference Manual(W483)
SSR
+
Contents
Specifies the number of input data bits.
Specifies whether S contains a duty ratio
or manipulated variable.
Specifies the input read timing.
Specifies whether the output limit function
is enabled or disabled.
Control period
(Time period in which the ON/OFF
changes are made.)
Specifies the lower limit when the output
limit is enabled.
Specifies the upper limit when the output
limit is enabled.
This work area is used by the system. It
cannot be used by the user.
Heater
AC
Setting range
0 hex: 8 bits
5 hex: 13 bits
1 hex: 9 bits
6 hex: 14 bits
2 hex: 10 bits
7 hex: 15 bits
3 hex: 11 bits
8 hex: 16 bits
4 hex: 12 bits
0 hex: Duty ratio
Setting range for S: 0000 to 2710 hex (0.00 to
100.00%)
1 hex: Manipulated variable
Setting range for S: 0000 to FFFF hex (0 to
65,535)
(The maximum setting depends on the MV range
set with bits 00 to 03 of C.)
0 hex: Use the beginning value of the control period
1 hex: Use lower value
2 hex: Use higher value
3 hex: Continuous adjustment
0 hex: Disabled
1 hex: Enabled (See note.)
0064 to 270F hex (1.00 to 99.99 s)
Note For example, 1.00 s is set as 0064 hex, and not
0001 hex.
0000 to 2710 hex (0 to 100.00%)
0000 to 2710 hex (0 to 100.00%)
Cannot be used.
2 Instructions
2
Change with
ON input
condition
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
---
2-271