Performance Specifications; Calculation Method - Omron SYSMAC CP Series Instruction & Reference Manual

Cpu unit
Hide thumbs Also See for SYSMAC CP Series:
Table of Contents

Advertisement

2 Instructions
Hint
• PIDAT(191) is executed as if the execution condition was a STOP-RUN signal. PID calculations are
executed when the execution condition remains ON for the next cycle after C+11 to C+40 are initial-
ized. Therefore, when using the Always ON Flag (ON) as an execution condition for PIDAT(191), pro-
vide a separate process where C+11 to C+40 are initialized when operation is started.
Precautions
• A PID parameter storage word cannot be shared by multiple PIDAT instructions. Even when the same
parameter is used in multiple PIDAT instructions, separate words must be specified.
• When changing the PID constants manually, set the PID constant change enable setting (bit 1 of
C+5) to 1 so that the values in C+1, C+2, and C+3 are refreshed each sampling period in the PID cal-
culation. This setting also allows the PID constants to be adjusted manually after autotuning.
• Of the PID parameters (C to C+40), only the following parameters can be changed when the execu-
tion condition is ON. When any other values have been changed, be sure to change the execution
condition from OFF to ON to enable the new settings.
• Set value (SV) in C
(Can be changed during PID control only. An SV change during autotuning will not be
reflected.)
• PID constant change enable setting (bit 1 of C+5)
• P, I, and D constants in C+1, C+2, and C+3
(Changes to these constants will be reflected each sampling period only if the PID constant
change enable setting (bit 1 of C+5) is set to 1.)
• AT Command Bit (bit 15 of C+9)
• AT Calculation Gain (bits 0 to 14 of C+9) and Limit-cycle Hysteresis (C+10) (These values are
read when autotuning starts.)

Performance Specifications

Item
PID control method
Number of PID control loops
Sampling period
PID constant
Proportional band
Integral constant
Derivative constant
Set value
Measured value
Manipulated variable

Calculation Method

Calculations in PID control are performed by the target value filtered control with two degrees of
freedom.
2-260
---
Target value filter-type two-degrees-of-freedom PID method (forward/reverse)
---
Unlimited (1 loop per instruction)
τ
0.01 to 99.99 s
P
0.1 to 999.9%
Tik
1 to 8191, 9999 (No integral action for sampling period multiple, 9999.)
Tdk
0 to 8191 (No derivative action for sampling period multiple, 0.)
SV
0 to 65535 (Valid up to maximum value of input range.)
PV
0 to 65535 (Valid up to maximum value of input range.)
MV
0 to 65535 (Valid up to maximum value of output range.)
Specifications
CP1E CPU Unit Instructions Reference Manual(W483)