Trane R Series Installation Operation & Maintenance page 148

R series rotary liquid chillers water-cooled and condenserless
Table of Contents

Advertisement

Table 28
Diagnostic Codes
Diagnostic Description
External Chilled Water Setpoint
External Current Limit Setpoint
EXV Elec. Drive CKT - Rfgt Ckt 1
EXV Elec. Drive CKT - Rfgt Ckt 2
High Diff. Press. - Ckt 1
High Diff. Press - Ckt 2
High Oil Temp - Cprsr A
High Oil Temp - Cprsr B
High Oil Temp - Cprsr C
High Oil Temp - Cprsr D
High Pressure Cutout - Cprsr A
High Pressure Cutout - Cprsr B
High Pressure Cutout - Cprsr C
High Pressure Cutout - Cprsr D
Loss of Local Display Panel COM
Low Chilled Water Temp (Unit off)
Low Chilled Water Temp (Unit on)
Low Differential Press - Ckt 1
Low Differential Press - Ckt 2
Low Evap Rfgt Temp - Ckt 1
Low Evap Rfgt Temp - Ckt 2
148
Diagnostics
Type
Cause
IFW
a.
b.
IFW
a.
b.
CMR
Run the EXV electrical drive circuit test both on demand from
the human interface and just before either a circuit or one of a
pair of circuits starts.
CMR
Same as Diagnostic for Ckt 1, above.
CMR
The difference between the Condenser pressure and the
evaporator pressure exceeded 350 PSID for 0.8-5.0 seconds.
320 PSID must hold, 320 + to trip in One Hour.
CMR
Same as Diagnostic for Ckt 1, above.
CMR
Entering Oil Temp to given compressor exceeded 170F . Time to
trip is given by equation: trip time = (190-0il Temp) x 180 sec/F .
CMR
Same as Cprsr A, above.
CMR
Same as Cprsr A, above.
CMR
Same as Cprsr A, above.
CMR
A high pressure cutout was detected on Cprsr A; trip at 405 +
or -7 PSIG.
CMR
A high pressure cutout was detected on Cprsr B; trip at 405 +
or -7 PSIG.
CMR
A high pressure cutout was detected on Cprsr C; trip at 405 +
or -7 PSIG.
CMR
A high pressure cutout was detected on Cprsr 0; trip at 405 +
or -7 PSIG.
IFW
The 1U1 has detected a loss of IPC communication with the
Local Display panel for at least 15 seconds.
IFW
The chilled water temp. fell below the cutout setpoint while the
compressors were not running.
MAR
The chilled water temp. fell below the cutout setpoint while the
compressors were running for 30 degree F Seconds.
CMR
The fan control algorithm detected a low differential Temper-
ature/Pressure condition that existed for more than 180
contiguous seconds. Trip point is 40 PSID.
CMR
Same as Diagnostic for Ckt 1, above.
CMR
a.
b.
CMR
Same as Diagnostic for Ckt 1, above.
Not "Enabled": no diagnostics.
"Enabled": Out-Of-Range Low, set diagnostic.
Out-Of-Range Hi, no diagnostic.
Not "Enabled": no diagnostics.
"Enabled": Out-Of -Range Low, set diagnostic.
Out-Of -Range Hi, no diagnostic.
The Saturated Evap Rfgt Temp - Circuit 1 dropped below
the Low Rfgt Temp Cutout Setpoint while the circuit was
running for 30 deg F seconds.
See the low ambient ignore time on startup.
RLC-SVX07A-EN