Diagnostics - Trane R Series Installation Operation & Maintenance

R series rotary liquid chillers water-cooled and condenserless
Table of Contents

Advertisement

Table 28
Diagnostic Codes
Diagnostic Description
Chilled Water Flow (Ent Wtr Temp)
Chilled Water Flow Interlock
Compressor Overload Setting Cprsr A
Compressor Overload Setting - Cprsr B
Compressor Overload Setting - Cprsr C
Compressor Overload Setting - Cprsr D
Cond Fan Var Speed Drive Fault Ckt 1
Cond Fan Var Speed Drive Fault Ckt 2
Cond Entering Wtr Temp Sensor
Cond Leaving Wtr Temp Sensor
Cond Rfgt Temp Sensor - CKT 1
Cond Rfgt Temp Sensor - CKT 2
146

Diagnostics

In the table below, a latching diagnostic is a condition which shall cause the
machine or a portion of the machine as noted to shut down and shall require a
manual reset to restore operation. A diagnostic that is non-latching shall reset
automatically when the condition causing the diagnostic goes away. A non-
latching diagnostic shall shut down the machine or a part of the machine if so
indicated. If a diagnostic is informative only, no machine or circuit action is
taken except to load a diagnostic code into the last diagnostic register.
Diagnostic Types (And Action)
MMR = Machine Shutdown, Manual Reset
MAR = Machine Shutdown, Auto Reset
CMR = Circuit Shutdown, Manual Reset
CAR = Circuit Shutdown, Auto Reset
IFW = Information Warning
Type
Cause
MMR
a.
b.
MAR
The chilled water flow switch input was open for more than 6
seconds.
IFW
The CPM NovRam Based overload setting did not agree with
the MCSP Dip Switch overload setting for 30 contiguous
seconds. The affected MCSP shall use the minimum (00000
binary, 00 decimal) overload setting as a default until the UCM
is reset when this diagnostic occurs.
I FW
Same as Cprsr A, above.
IFW
Same as Cprsr A, above.
IFW
Same as Cprsr A, above.
IFW
The controlling MCSP for the given circuit has unsuccessfully
attempted (5 times within 1 minute) to clear a fault signal from
the Condenser Fan Inverter Drive. The 5th attempt removes
power from the inverter to create a power up reset. If the fault
does not clear, the UCM will revert to constant speed
operation without the use of the inverters fan. The inverter
must be manually bypassed for full fixed speed fan operation.
IFW
Same as Ckt 1, above.
IFW
Shorted Cond. temp sensor. No diagnostic on open.
IFW
Shorted Cond. temp sensor. No diagnostic on open.
CMR
Open or short.
CMR
Open or short.
The entering evaporator water temp. fell below the
leaving evaporator water temp. by more than 2F for 100
degree F - seconds.
Causes to trip this diagnostic include either a loss of
chilled water flow or a calibration shift in the evap. water
temp. sensors.
RLC-SVX07A-EN