Trane R Series Installation Operation & Maintenance page 117

R series rotary liquid chillers water-cooled and condenserless
Table of Contents

Advertisement

RLC-SVX07A-EN
Controls Interface
Table 26
Leaving Fluid Temperature Setpoints
The leaving chilled water temperature is not the same as the ice termination setpoint. The
ice termination setpoint is based on entering chilled water temperature. Therefore, the ice
termination setpoint, minus temperature drop across the evaporator while in the ice
making mode, equals the leaving chilled water temperature.
Leaving
Leaving
Chilled Water
Water Temp
Temp - F
Cutout - F
40
35
39
34
38
33
37
32
36
31
35
30
34
29
33
28
32
27
31
26
30
25
29
24
28
23
27
22
26
21
25
20
24
19
23
18
22
17
21
16
20
15
19
14
18
13
17
12
16
11
15
10
14
9
13
8
12
7
11
6
10
5
9
4
8
3
7
2
6
1
5
0
4
-1
3
-2
2
-3
1
-4
0
-5
***Recommended% Ethylene Glycol will give freeze protection consistent with other chiller
safety controls (solution freeze point is nominally 10'F above refrig temp cutout).
Low
Refrig Temp
Recommended***
Cutout - F
% Ethylene Glycol
22
0
20
3
18
6
17
8
15
10
14
12
12
14
11
15
9
17
7
19
6
20
4
21
2
23
0
25
-1
26
-3
28
-5
29
-6
30
-8
31
-10
33
-11
34
-13
35
-15
36
-17
37
-18
38
-19
39
-21
40
-23
41
-24
42
-26
43
-27
43
-29
44
-31
45
-32
46
-34
47
-35
47
-37
48
-38
49
-39
50
-39
50
-39
50
Solution Freeze
Point - F
32
25
21
16
10
4
-3
-11
-21
-32
117