Trane R Series Installation Operation & Maintenance page 147

R series rotary liquid chillers water-cooled and condenserless
Table of Contents

Advertisement

Table 28
Diagnostic Codes
Diagnostic Description
Contactor CPRSR A
Contactor CPRSR B
Contactor CPRSR C
Contactor CPRSR D
CPRSR Suct Temp Sensor - Ckt 1
CPRSR Suct Temp Sensor - Ckt 2
CWS/Leaving Water Temp Cutout
Setpoint Overlap
Discharge Temp - Cprsr A
Discharge Temp - Cprsr B
Discharge Temp - Cprsr C
Discharge Temp - Cprsr D
Emergency Stop
Entering Oil Temp Sensor - Cprsr A
Entering Oil Temp Sensor - Cprsr B
Entering Oil Temp Sensor - Cprsr C
Entering Oil Temp Sensor - Cprsr D
Evap Entering Wtr Temp Sensor
Evap Leaving Wtr Temp Sensor
Evap Rfgt Temp Sensor - CKT 1
Evap Rfgt Temp Sensor - CKT 2
RLC-SVX07A-EN
Diagnostics
Type
Cause
MMR
a.
b.
MMR
Same as CPRSR A.
MMR
Same as CPRSR A.
MMR
Same as CPRSR A.
CMR
Open or short.
CMR
Open or short.
None
No diagnostic, display to flash and 1imit value to last legal
value.
NOTE: The above is not a diagnostic because you
don't want the display vectoring you to a different
display state when you are trying to set either the
chilled water setpoint or the leaving water temp.
cutout setpoint as it will in the case of a diagnostic.
CMR
a.
b.
c.
CMR
Same as Diagnostic for Cprsr A, above.
CMR
Same as Diagnostic for Cprsr A, above.
CMR
Same as Diagnostic for Cprsr A, above.
MMR
EMERGENCY STOP input is open. An external interlock has
tripped. Time to trip from input opening to unit stop shall be
0.1 to 1.0 seconds.
CMR
Open or short.
CMR
Open or short.
CMR
Open or short.
CMR
Open or short.
MMR
Open or short.
MMR
Open or short.
CMR
Open or short (for 30 sec).
CMR
Open or short (for 30 sec).
Welded cprsr contactor.
Detected a welded compressor contactor when the
compressor was commanded off but the current does
not go to zero. Detection time shall be 5 second
minimum and 10 seconds maximum. On detection,
generate the diagnostic, energize the appropriate alarm
relay, continue to command the affected compressor off,
energize the affected compressors oil line solenoid, stop
all other compressors, unload the running compressor
with the welded contactor, open the EXV to its
maximum open position, and continue to do fan control.
Do not exit this condition until the controller is manually
reset.
The discharge temp. exceeded the trip value;
135 + or -3 C.
The discharge temp. PTC or wiring is open.
Time to trip from either trip value exceeded or input
open shall be 0.5 to 2.0 seconds.
147