Trane Tracer ZN.520 Installation Owner Diagnostics page 66

For classroom unit ventilator
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

Hardwired Setpoint Adjustment
Table 35: Hardwired setpoint adjustment
Resistance ( )
Setpoint (Deg F)
889.4
50
733.6
58
577.9
66
500
70
422.1
74
344.2
78
266.4
82
188.5
86
110.6
90
Fan Switch Resistance Values
Table 36: Resistance values
Resistance ( )
16,300
10,700
2,320
4,870
Hardwired Thermistor Values
Table 37: Hardwired 10k
thermistor values
Resistance
Temperature
87.5k
0 F
74.6k
5 F
63.8k
10 F
54.6k
15 F
46.9k
20 F
40.4k
25 F
34.8k
30 F
30.2k
35 F
26.2k
40 F
22.8k
45 F
20.0k
50 F
17.5k
55 F
15.3k
60 F
13.5k
65 F
11.9k
70 F
10.5k
75 F
60
Appendix
Switch Position
High
Low
Auto
Off
Resistance
Temperature
10.0k
77 F
9.3k
80 F
8.2k
85 F
7.3k
90 F
6.5k
95 F
5.8k
100 F
5.2k
105 F
4.7k
110 F
4.2k
115 F
3.8k
120 F
3.4k
125 F
3.1k
130 F
2.8k
135 F
2.5k
140 F
2.3k
145 F
2.1k
150 F
UV-SVP01A-EN