Trane Tracer ZN.520 Installation Owner Diagnostics page 56

For classroom unit ventilator
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

.
Table 27: Test sequence for face-and-bypass unit configurations
Step
Fan
J1-1
J1-2
1: Off
Off
Off
1
2: Fan high
High
Off
2
3: Fan med
Off
Med
3
4: Fan low
Off
Off
4
5: Main open,
High
Off
DX on
6: Main close,
DX off, aux
High
Off
open
7: Aux open,
High
Exh
exhaust fan
5
8: Aux close,
High
Off
damper open
9: Outdoor air
High
Off
damper close
10: Generic /
baseboard heat
High
Off
energized
11: Exit
6
1. Upon entering manual output test mode, the controller turns off all fan outputs and drives all dampers and valves closed (if required).
2. At the beginning of step 2, the controller attempts to clear all diagnostics.
3. If the unit is configured for a 2-speed fan, the fan remains on high speed at step 3.
4. If the unit is configured for a 2-speed fan, the low fan speed output energizes at step 3. If the unit is configured for a 1-speed fan, the fan
remains on high speed at step 3.
5. If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The exhaust fan output is shared with medium
fan speed.
6. After step 10, the test sequence performs an exit. This initiates a reset and attempts to return the controller to normal operation.
UV-SVP01A-EN
Troubleshooting
DX, or cool or heat/
cool changeover valve
J1-3
J1-5
J1-6
Off
Off
NA
Off
Off
NA
Off
Off
NA
Low
Off
NA
Off
On
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
Face-and-
Electric heat,
bypass damper
or heat valve
J1-7
J1-8
J1-9
J1-10
Off
On
Off
On
Off
Off
On
Off
Off
On
Off
Off
On
Off
Off
On
Off
On
On
Off
On
Off
On
Off
Off
On
Off
Off
On
Off
Exit
Generic/
Outdoor air
baseboard
damper
J1-11
J1-12
TB4-1
NA
Off
On
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
Off
Off
NA
On
Off
NA
Off
On
NA
Off
Off
heat
Off
Off
Off
Off
Off
Off
Off
Off
Off
On