Table 2: End Device Specifications
Device
Outside Air Actuator
Face and Bypass Actuator
2-way Control Valve
14
Standard End Devices
Characteristic
Description
Ambient Temperature Rating
Power Consumption
Torque
Drive Time
Description
Ambient Temperature Rating
Power Consumption
Torque
Drive Time
Description
Ambient Temperature Rating
Drive Time
Max Pressure
Close Off
Temperature
Description
Three-point floating with spring return
-25°F to 125°F
5 VA
35 in-lbs.
90 seconds, 95 degree stroke
Three-point floating
32°F to 122°F
3 VA
35 in-lbs.
80-110 seconds, 95 degree stroke
Three-point modulating
140°F at 95% relative humidity
50 seconds
400 psi water
Varied by size and Cv
Water 200°F maximum