Trane Tracer ZN.520 Installation Owner Diagnostics page 10

For classroom unit ventilator
Hide thumbs Also See for Tracer ZN.520:
Table of Contents

Advertisement

Table 2: End Device Specifications
Device
Fan Status Switch
Low Temperature Detection Switch (Freezestat)
OutsideAir Sensor/discharge AirSensor/Entering
Water Temperature Sensor/Unit Mounted, Zone
Return-air Temperature Sensor
UV-SVP01A-EN
Standard End Devices
Characteristic
Material
Operating Temperature Range
Contact Form
Preset
Trip Temperature:
Release Temperature
Rating—Auto Reset
Sensing Element
Description
Contact Blade—Pilot duty rated
-40°F/250°F (-40°C/120°C)
SPST-NO
Fan status - 0.07"
3 6 ° F ± 2 ° F
(2°C + - 1.11°C)
4 4 ° F ± 3 ° F
(6.67°C + - 1.67°C)
Pilot Duty
120 VAC
240 VAC
(24 VAC)
FLA
10.0
5.0
LRA
60.0
30.0
Thermistor 10 KOhms @ 77°F ± 1.8°F (25°C
±1°C)
13