Standard Delivery - Viessmann KOB PYROTEC Technical Manual

Grate combustion 390 to 1250 kw, fully automatic wood boiler, for the combustion of woodchips, pellets, shavings and mixed wood
Table of Contents

Advertisement

Control unit
(cont.)

Standard delivery:

■ Control panel loose; surface powder-coated. Version as per ÖVE/
VDE directives fully wired to terminal strips, fed 3 x 400 V 50 Hz;
control voltage 230 V or 24 V;
– Freely programmable control unit, CE tested
– Motor overload relay for all drives according to the separate price
item
– Inverter for fan motors
– Motor overload relay for boiler pump
■ In the control panel door:
– 4-pole main isolator
– 8" touch-screen, 640 x 480 mm
– Documentation incl. fixed wiring diagram, terminal connection dia-
gram with cable designation, operating and maintenance instruc-
tions, and installation instructions in a plan wallet
■ Sensors and switches installed at the supply screw conveyor:
– Infrared light barrier, level monitoring, separating barrier, supply
screw conveyor
– Safety limit switch on inspection cover of supply screw conveyor
– Contact sensor PT-100 at the supply screw conveyor
3
14
■ Sensors and switches at the combustion block and in the flue outlet
(installation on site):
– Combustion chamber temperature sensor NiCrNi
– Infrared light barriers, level monitoring, fuel in combustion cham-
ber
– Zirconium dioxide probe with measured value transducer (Lambda
probe)
– Flue gas temperature sensor PT-100
– Underpressure sensor
– Overpressure limiter
■ Sensors and switches installed at top of boiler:
– Boiler water temperature sensor PT-1000 in connector flow
– Return temperature sensor PT-1000 in connector return
– High limit safety cut-out
PYROTEC

Advertisement

Table of Contents
loading

Table of Contents