Fuel Discharge By Means Of Funnel Discharge - Viessmann KOB PYROTEC Technical Manual

Grate combustion 390 to 1250 kw, fully automatic wood boiler, for the combustion of woodchips, pellets, shavings and mixed wood
Table of Contents

Advertisement

Design information
(cont.)

6.13 Fuel discharge by means of funnel discharge

Funnel discharge
Material discharge for round silos is carried out with an agitator inte-
grated in the discharge casing. In its centre, the discharge screw is
driven via a solid universal joint. When the silo is full, the screw con-
veyor moves into a vertical position. The funnel limits the angle of the
screw conveyor when the silo is empty. Drive is via a spur geared
conveyor motor to the agitator. In the case of material compression in
the discharge casing, as a result of increased drive power consump-
tion, the supply direction of the screw conveyor is changed automati-
cally for a period set at the factory. This releases the compression,
preventing a fault.
Version and drives
Funnel discharge
Part no.
Diameter, discharge circuit, max.
Boiler outputs with
Pellets S 650
Woodchips from forest S 200
Shavings S 130
Torque at screw conveyor
2,21 mm
57,48 mm
95
PYROTEC
Standard delivery:
■ Funnel discharge as per order data with drive unit 3 x 400 V
■ Automatic control of the drive for the spur geared conveyor motor for
both rotational directions
■ Safety limit switch installed on inspection cover of discharge casing
ø a
2,26 mm
ø b
95
AP-11
7837 899
m
6.0
kW
3000
kW
1250
kW
1250
Nm