Extinguishing Water Container; Extinguishing Facility With Cold Water Supply; Back Burning Protection, Boiler System - Viessmann KOB PYROTEC Technical Manual

Grate combustion 390 to 1250 kw, fully automatic wood boiler, for the combustion of woodchips, pellets, shavings and mixed wood
Table of Contents

Advertisement

Design information

Extinguishing water container

Part no. 7387 785
D
A N25 fill level monitoring
B Extinguishing water container 25 l

Extinguishing facility with cold water supply

Part no. 7388 521
6
A
B
A Combustion
B Dosing container with separating barrier
KW Cold water supply DN 15 ½" min. 2.0 bar, max. 3.0 bar
Note
■ Lines should be secured in metal pipes (½").
■ The cold water supply must not be able to be isolated without the aid
of a tool.

Back burning protection, boiler system

The boiler system back burning protection is part of the standard deliv-
ery.
40
(cont.)
A
B
C
KW
C Material supply
D Combustion
Note
Part of the boiler.
Note
■ Adjustment, valve, Danfos AVTA 15 50–90 °C
3 corresponds to 80 C°.
■ Lines should be secured in metal pipes (½").
■ The cold water supply must not be able to be isolated without the aid
of a tool.
KW
A
B
Note
Alternative or additional safety equipment. A shut-off gate valve is
required as standard for an unpressurised material store or a rotary
lock valve for a material store with overpressure or underpressure
(charging with fan, e.g. wood processing operations).