Viessmann VITOCAL WPR 300 Service Instructions Manual
Viessmann VITOCAL WPR 300 Service Instructions Manual

Viessmann VITOCAL WPR 300 Service Instructions Manual

Heat pump control unit manual
Table of Contents

Advertisement

VIESMANN
Service instructions
for contractors
Vitocal
WPR 300 heat pump control unit manual
For applicability, see the last page
VITOCAL
Please keep safe.
5366 335 GB
8/2008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VITOCAL WPR 300 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Viessmann VITOCAL WPR 300

  • Page 1 VIESMANN Service instructions for contractors Vitocal WPR 300 heat pump control unit manual For applicability, see the last page VITOCAL Please keep safe. 5366 335 GB 8/2008...
  • Page 2: Safety Instructions

    The system must be commissioned promise the safe operation of by the system installer or a qualified your heating system. person authorised by the installer. Replace faulty components only with original Viessmann Regulations spare parts. Observe the following when working on this system &...
  • Page 3 Instal- ling non-authorised compo- nents and non-approved modifications or conversions can compromise safety and may invalidate our warranty. For replacements, use only ori- ginal spare parts supplied or approved by Viessmann.
  • Page 4: Table Of Contents

    Index Index Introduction ....................Function description Heat pump ....................11 Lag heat pumps ..................15 External heat source ................... 16 DHW cylinders.................... 17 Instantaneous heating water heater ............23 Heating water buffer cylinder............... 24 Heating circuit .................... 28 Cooling mode in cooling or heating circuit ........... 35 Swimming pool ...................
  • Page 5 Index Index (cont.) Compressor control settings Compressor control settings ............... 91 5000 Enabling ! ..................91 5001 Max. flow temp §................91 5002 Min. return temp. §................92 5004 Hysteresis primary § ................. 93 5005 Min. runtime §................... 93 5006 Min. pause §..................94 5008 Start delay §...
  • Page 6 Index Index (cont.) 7B05 Mixer t limit § ..................112 7B06 Min. runtime § .................. 112 7B07 Runtime without demand § ............... 113 7B08 Mixer runtime § ................113 7B09 Mixer active zone § / 7B0A Mixer dead zone §......... 114 7B0B Flow t excess §...
  • Page 7 Index Index (cont.) 7305 Integral 3-way valve § ............... 134 7306 Prop. 3-way valve § ................135 7307 Max. step 3-way v § ................135 7308 Heat p night op § ................136 7309 Heat pump run-on § ................136 730B Sec pump run-on §...
  • Page 8 Index Index (cont.) 7103 Min. flow temp. ! ................155 7104 Room t hook-up slope ! ..............156 7105 Room control § ................. 156 7106 Ranking RTS § ................. 157 7107 Room t hyster.cool § ................. 157 7108 Integral room thermostat § ..............157 7110 Cooling curve level ! / 7111 Cooling curve slope ! ......
  • Page 9: Introduction

    Introduction This manual explains the function, control parameters and fault messages of the WPR 300 heat pump control unit for Viessmann heat pumps. With the control parameters, the heat pump can be matched to varying demands and operating conditions. To avoid incorrect operation of the heat pump or other system components, the control parameters and fault messages are available at three different setting levels.
  • Page 10 Menu item cialist knowledge in relation to & "Device settings" & "Access rights" Viessmann heat pumps. Our warranty becomes void if incor- & Enter the code using the selec- rect operation occurs at the "Con- tion keys: tractor" or "Expert" setting level by the 5243 for "Contractor"...
  • Page 11: Heat Pump

    Function description Heat pump The WPR 300 heat pump control unit is suitable for the following heat pumps: & Vitocal 300-G, type BW, BWC, WW, WWC & Vitocal 300-A, type AWC-I, AW-O Different parameters are available in the control unit subject to type and equip- ment level.
  • Page 12: Function Description Heat Pump

    Function description Heat pump (cont.) If the compressor does not start & Power-OFF is enabled. because of a fault, the control unit & The heat pump has a fault. switches on other heat sources as Frequently stopping and starting the available.
  • Page 13 Function description Heat pump (cont.) For optimised starting and stopping of compressor stage 2, the heating out- puts of the individual compressor stages must be known. This is speci- fied with parameter "Output" (5030, 5130). Refrigerant circuit The operating conditions in the refrig- For control of the refrigerant circuit, erant circuit are generally influenced the following factors are taken into...
  • Page 14 Function description Heat pump (cont.) To assess the efficiency, the power If the runtimes of electrical heat consumption calculated for the com- sources are too long in spite of opti- pressor can be compared with the mum matching, the following must be total heat pump consumption for the checked more closely: same period.
  • Page 15: Lag Heat Pumps

    Function description Heat pump (cont.) & Temperature differential for the start & Evaporator temperature for the start of the defrost process ("Temp. diff. of the defrost process ("Defrost defrost", 500E) start t", 500F) & Max. evaporator temperature ("Defrost stop t", 5010). Lag heat pumps The heat pump control unit in the lead appliance can regulate up to four lag heat pumps, subject to connection method.
  • Page 16: External Heat Source

    Function description Lag heat pumps (cont.) Lag heat pumps are hydraulically con- Lag heat pumps can be enabled via trolled in a cascade, which supplies parameter "Priority ext. demand" the heating circuits directly or via a (7019) for swimming pool heating. heating water buffer cylinder.
  • Page 17: Dhw Cylinders

    Function description External heat source (cont.) & The outside temperature (long-term If, after starting, the flow temperature average) is below the "Dual-mode in the circuit of the external heat temp" (7B02). source reaches the temperature & The actual value for "Threshold" "Mixer t limit"...
  • Page 18 Function description DHW cylinders (cont.) Cylinders with an internal indirect coil Note ("coil heat exchanger"), external heat 3 K additional differential between the exchanger (cylinder primary system) heating water flow temperature and and cylinders with jacket heat exchan- cylinder temperature reduce the effi- gers can be used.
  • Page 19 Function description DHW cylinders (cont.) For cylinder primary systems, mixing of the cylinder water and cooling of the return is prevented, because the cylinder primary pump only starts when the flow time of the secondary pump ("Start delay", 5008) is reached and the heat pump produces heating output.
  • Page 20 Function description DHW cylinders (cont.) Booster heaters Booster heaters, e.g. an immersion & Cylinder temperature is below 3 °C heater, external heat source or instan- (frost protection). taneous heating water heater can be & Heat pump does not provide any used for DHW heating.
  • Page 21 Function description DHW cylinders (cont.) Frost protection As soon as the temperature at the top cylinder temperature sensor drops below 3 °C, the heat pump control unit switches the DHW cylinder into frost protection mode. This is independent of the set temperatures of the different operating modes.
  • Page 22 Function description DHW cylinders (cont.) DHW auxiliary function By regularly heating the DHW cylin- der, the auxiliary function ("Auxiliary function", 600B) offers effective pro- tection from possible bacteria. For this, the total contents of the DHW cylinder are heated to "Set temp. 2" (600C) during the first DHW heating on a Monday.
  • Page 23: Instantaneous Heating Water Heater

    Function description DHW cylinders (cont.) Forced heat transfer Minimum compressor runtimes The forced heat transfer also ends increase the efficiency and protect the when "Max. temp" (6006) is reached. components of the heat pump. Sur- plus heat can be transferred to the consumers, as soon as they receive a "transfer signal"...
  • Page 24: Heating Water Buffer Cylinder

    Function description Instantaneous heating water heater (cont.) If enabled via parameter "Max. e To limit the total power consumption, heating stage" (7907), the control the control unit stops the instanta- unit starts stages 1, 2 or 3 of the neous heating water heater for a few instantaneous heating water heater, seconds directly before the compres- subject to heat demand.
  • Page 25: Operating Modes

    Function description Heating water buffer cylinder (cont.) For system diagrams 3 to 10, the In contrast to the heating circuits, the heating water buffer cylinder is config- heating water buffer cylinder is regu- ured automatically, since it is a con- lated by output and not temperature.
  • Page 26 Function description Heating water buffer cylinder (cont.) & "Off" & "Standard" and "Reduced" In "Standby" mode, the control unit The temperature at the cylinder monitors the frost protection of the temperature sensor is used for the heating water buffer cylinder. If the heat demand.
  • Page 27: Stop Optimisation

    Function description Heating water buffer cylinder (cont.) Demand of further heat sources Under certain conditions, to heat the Enabling only if the outside tem- heating water buffer cylinder, the con- perature is below the dual-mode trol unit issues a demand to other heat temperature ("Dual-mode temp", sources as well as the heat pump.
  • Page 28: Heating Circuit

    Function description Heating water buffer cylinder (cont.) Forced heat transfer Minimum compressor runtimes The forced heat transfer for the heat- increase the efficiency and protect the ing water buffer cylinder is ended as components of the heat pump. Sur- soon as the temperature in the cylin- plus heat can be transferred to the der or the return temperature exceeds consumers, as soon as they receive a...
  • Page 29 Function description Heating circuit (cont.) Subject to the outside temperature, Fixed hystereses are programmed to the control unit switches between prevent brief fluctuations around heating, cooling and frost protection these limits from resulting in continual mode. For heating and cooling mode, changeover between heating and the start and stop limits required here cooling mode.
  • Page 30 Function description Heating circuit (cont.) A Temperature differential for calcu- E Set room temperature (adjustable via rotary selector s or m) lating the cooling limit ("Temp. F Frost limit ("Frost protection t", diff. cooling", 7004) B Temperature differential for calcu- 7006) G Frost protection mode enabled lating the heating limit ("Temp.
  • Page 31 Function description Heating circuit (cont.) "Standby operating mode" In "Standby" operating mode, heating & Short-term average outside tem- is carried out if one of the following perature exceeds the limit "Frost criteria is met: protection t" (7006) by at least 2 K. &...
  • Page 32 Function description Heating circuit (cont.) Weather-compensated control ΔT In weather-compensated heating Room temperature - out- ATS/RTS mode, the set flow temperature in side temperature differen- both operating modes is calculated tial (long-term average) ΔT from the relevant set room tempera- Room influence ΔT ture "Room t standard"...
  • Page 33 Function description Heating circuit (cont.) Max. flow temperature The maximum possible set flow tem- perature for both weather-compen- sated and room temperature- dependent control is specified by parameter "Max. flow temp." (200E). Temperature control ϑ = ϑ – 5 K Heating circuits with mixer are regu- RL, set VL, set...
  • Page 34 Function description Heating circuit (cont.) Demand of further heat sources Under certain conditions, the control Parameter "Ext. heat source" unit issues a demand to other heat (7B00) is set to "Yes" and tem- sources as well as the heat pump, e. perature is below dual-mode tem- g.
  • Page 35: Cooling Mode In Cooling Or Heating Circuit

    Function description Heating circuit (cont.) Forced heat transfer Minimum compressor runtimes Note increase the efficiency and protect the The forced heat transfer for one heat- components of the heat pump. Sur- ing circuit ends as soon as the maxi- plus heat can be transferred to the mum flow temperature "Max.
  • Page 36 Function description Cooling mode in cooling or heating circuit (cont.) The system diagrams for cooling Note mode are hydraulically sized so the For active cooling, a room tempera- cooling energy can directly reach the ture sensor must be installed and heating or cooling circuit.
  • Page 37 Function description Cooling mode in cooling or heating circuit (cont.) Note For cooling mode in the following cases, a room temperature sensor must be installed and enabled (para- meter "Remote control", 2003 set to "Yes"): & Weather-compensated cooling mode with room influence &...
  • Page 38 Function description Cooling mode in cooling or heating circuit (cont.) Room temperature-dependent control Parameter "Room control" (7105) Cooling mode for room temperature- enables room temperature-dependent dependent cooling mode starts as control for cooling mode. The set flow soon as the room temperature is temperature is calculated from the dif- above the set room temperature ferential of the set and actual room...
  • Page 39: Swimming Pool

    Function description Swimming pool The control unit backs up separate swimming pool heating ("Swimming pool", 7008). If the value of parameter "Priority Installation/service instructions ext. demand" (7019) is "No", the swimming pool has the lowest priority The control unit starts swimming pool compared to all other consumers.
  • Page 40: Troubleshooting Control Unit Diagnostics

    Troubleshooting Control unit diagnostics Scanning messages A Fault display B Message C Message symbol Messages are displayed by the mes- Note sage symbols («, ¸, !) flashing. For In this view, the setting level "Cus- faults (U), the fault indicator also tomer"...
  • Page 41 Troubleshooting Control unit diagnostics (cont.) Displaying and acknowledging messages & Acknowledged messages are Press the following keys: marked with ¡. The message and message symbol on the standard 1. To log on as "Contractor" or display are cleared. In case of "Expert", see page 10.
  • Page 42 Troubleshooting Control unit diagnostics (cont.) 6. "MESSAG" to return to the mes- Deleting message history sage display. Press "Reset". Message overview All messages that occur for all heat pump types are listed below. Not every mes- sage can occur for all types. The messages are identified by a two-digit code. Description of suitable measures Installation/service instructions Note...
  • Page 43 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Configuration Incorrect configuration of Check and match asso- fault system components; pos- ciated parameters, reset to sible causes: delivered condition if re- & External heat source quired ("Reset", see oper- enabled and NC-Box ating instructions), and mixer controlled directly reconfigure system.
  • Page 44 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures ¸07 Message EEV Message from EEV con- Observe messages in heat troller, compressor stage 1 pump module diagnosis (see page 59). ¸08 Message EEV Message from EEV con- Observe messages in heat troller, compressor stage 2 pump module diagnosis (see page 59).
  • Page 45 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Flow sensor Type BW/WW Check pressure drop value & primary Short circuit - primary (Pt 500) at connections circuit flow temperature 3X1.24 and 3X2.24; re- sensor (heat pump inlet) place sensor if required. Type AW &...
  • Page 46 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Primary return Type BW/WW Check pressure drop value & sens. Break - primary circuit (Pt 500) at connections return temperature sen- 3X1.24 and 3X2.24; re- sor (heat pump outlet) place sensor if required. Type AW &...
  • Page 47 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Flow sensor Break, flow temperature Check pressure drop value sensor heating circuit M3 (Ni 500) at extension kit (see table below F) connections for heating cir- cuit with mixer; replace sensor if required. Flow sensor Break, system flow tem- Check pressure drop value...
  • Page 48 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Ext. heat Short circuit, external heat Check pressure drop value source source temperature sen- (Pt 500) at connections 3X1.4 and 3X2.4; replace (see table below L) sensor if required. Buffer cylinder Break, buffer cylinder tem- Check pressure drop value sensor perature sensor...
  • Page 49 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Room sensor Break - natural cooling Check pressure drop value room temperature sensor (type Ni 500) at connec- tions 3X1.6 and 3X2.6; re- place sensor if required. Collector sen- Short circuit, Vitosolic col- Check sensor and replace if lector temperature sensor required (see Vitosolic in-...
  • Page 50 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Heat pump Heat pump fault Scan further messages & Heat pump faulty ("Message history" see & Safety high pressure page 41); check volume switch has activated flow rates, motor currents/ & Control high pressure or motor protection, and low pressure switch has safety high pressure...
  • Page 51 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures UAD Mixer heat./ Three-way diverter valve Check three-way diverter "central/DHW heating" valve and replace if re- faulty quired. ¸AE DHW sensors Cylinder temperature sen- No measures required. The swapped sors top/bottom inter- control unit interchanges changed (!) the sensors internally.
  • Page 52 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures & KM BUS Solar Communication error - KM Check parameter BUS solar control unit, or "Vitosolic type" (7016). & sensor S3 of Vitosolic Check connection to faulty Vitosolic. & Check sensor S3 and replace if required.
  • Page 53 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures & Refrigerant Fault - refrigerant circuit, Check flow and return circuit compressor stage 1; high temperature sensors in limit safety cut-out has re- primary and secondary sponded circuits. & Check primary and sec- ondary circuits for pres- sure and throughput (see also fault UA9).
  • Page 54 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures UCC Coding card & Coding card cannot be Check coding card and read. replace if required. & Check PCB 2 (main PCB) and replace if required. & Check programming unit of heat pump control unit and connecting cable;...
  • Page 55 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Low pressure Low pressure fault - com- Type BW/WW & pressor stage 1 Reset pressure switch; check pressure gauge, Type BW/WW primary pump and shut- & Primary circuit leaks or off facilities. &...
  • Page 56 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Flow switch Primary circuit flow switch Type BW & has responded. Check primary pump. Type WW & Check immersion pump. & Check frost protection switch and heat exchan- ger in intermediate circuit. UDA Compressor 2 &...
  • Page 57 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures Low pressure Low pressure fault - com- Type BW/WW & pressor stage 2 Reset pressure switch; check pressure gauge, Type BW/WW primary pump and shut- & Primary circuit leaks or off facilities. &...
  • Page 58 Troubleshooting Control unit diagnostics (cont.) Message Cause Measures UDE Primary Fault - primary circuit, Type BW & source 2 compressor stage 2 Reset thermal relay, check primary pump and Type BW replace if required. & & Flow rate in primary cir- Check safety equipment cuit too low (frost protection brine...
  • Page 59 Troubleshooting Control unit diagnostics (cont.) Message System characteristics U21 ... Operation with temperature value of flow temperature sensor in U29 ... secondary circuit, minus 5 K. If both temperature sensors (sec- ondary flow and return) are faulty, the heat pump is stopped (message UA9).
  • Page 60 Troubleshooting Control unit diagnostics (cont.) The diagnosis function of the heat pump control unit displays important features of the EEV controller. Along with status and fault information, these also include the last temperature and pressure values directly before the compressor shut- down.
  • Page 61 Troubleshooting Control unit diagnostics (cont.) Information code part 1 (commands) Group 1 (1st and 2nd digits from the left) Com- Status Versions 01 Enable EEV controller mands 02 Enable EVI control circuit 04 Cooling mode enabled 40 Refrigerant circuit parameters reset by EEV controller Part 1 of the information code shows the most recent commands that the...
  • Page 62 Troubleshooting Control unit diagnostics (cont.) 40 Enable EEV controller via digital Group 4 (7th and 8th digits) input 01 Compressor shutdown due to fault 80 Cooling mode enabled via digital input Information code part 3 (versions) Note The hardware and software versions Commands Status Versions...
  • Page 63 Troubleshooting Control unit diagnostics (cont.) Part 2 of the fault information code Group 2 (3rd and 4th digits) contains two groups which display the As per fault information code part 1 fault location in the refrigerant circuit. The first two digits of the code are Group 3 (5th and 6th digits) identical to part 1, but are accepted No function.
  • Page 64 Troubleshooting Control unit diagnostics (cont.) Note While the compressor is running, the control unit in this overview continu- ously displays the current test values. After the compressor has shut down, the last values measured during operation can be called up. Hours run The compressor hours run given in Line...
  • Page 65 The first screen has the tion, commissioning and fault analy- description "BUS settings"; all fol- sis. All terms in LON technology are lowing screens have the title "LON explained in detail in the Viessmann diagnosis". LON manual. Menu &...
  • Page 66 Domain Network domains, data is hexadecimal, last digit specifies length of the domain designation used. Allocated via "Binding tool". Preset in Viessmann control units to the value 07 and length 1. Subnet Subnet address Allocated via "Binding tool".
  • Page 67 Page 5 is only visible if a heat pump cascade is installed via LON and configured. Page 1 Display Description SN neuron Neuron chip - Viessmann part number SN foreign Communication coprocessor - Viessmann part number Netconfig Configuration status: 0 "Self binding": Logical linking during installation was carried out via integral installation program.
  • Page 68 "Receive heartbeat" (779C). Obj. status Object status: Value of network variable "nvoNodeStatus"; see Viessmann LON manual, in brackets: Internal software code without function. SKO status Software communication status: K LON communication module installed; parameter 7710 set to "Yes".
  • Page 69 18 nviHcc3SpaceSet 19 nviHcc3FlowTemp 20 nviPM1BlrState 21 nviPM1SupplyT 22 nviPM1BoCState 23 nviPM2BlrState 24 nviPM2SupplyT 25 nviPM2BoCState 26 nviPM3BlrState 27 nviPM3SupplyT 28 nviPM3BoCState 29 nviPM4BlrState 30 nviPM4SupplyT 31 nviPM4BoCState For a description of the network variables, see the Viessmann LON manual.
  • Page 70 "Receive heartbeat" (779C). Obj. status Object status: Value of network variable "nvoNodeStatus"; see Viessmann LON manual > / < Precedes sizes displayed: > Value was received. < Value was sent. Setting via parameters "Outside temp" (7797) and "Time"...
  • Page 71 Status of the temperature 7 "Automatic" sensor; see page 70. Set flow temperature System production status; Specification for set flow see Viessmann LON man- temperature is the maxi- ual. mum value. Actual system flow tem- Status of the temperature perature sensor;...
  • Page 72 LON operating mode For heat pump cascades via LON, the (SNVT_hvac_mode); see lead appliance must have the LON Viessmann LON manual. communication module for heat pump Operating mode; see cascades installed. If an incorrect page 71. LON module is plugged in, fault mes- &...
  • Page 73 Troubleshooting Control unit diagnostics (cont.) Display Description Display Description Set flow temperature of the Actual flow temperature of secondary circuit of the lag the secondary circuit of the heat pump lag heat pump Status of the temperature Status of the temperature sensor;...
  • Page 74: No. External Heat Pumps

    Control settings - system definition 5735 No. external heat pumps ! No. lag heat pumps in a cascade. The control unit supports heat pump "1" to "4" cascades which are connected via No. lag heat pumps for connec- LON or via external extension H1. tion via LON.
  • Page 75 Control settings - system definition 7000 System diagram ! (cont.) System diagram Heating circuit – – – – – – – – – – – – – – – – – – – – – – — – DHW cylin- –...
  • Page 76 Control settings - system definition 7000 System diagram ! (cont.) X Required components System examples - heat 0 Optional components pumps Note Menu & The cooling option can only be used & "Device settings" respectively on one heating or cool- &...
  • Page 77: Temp. Diff. Heating

    Control settings - system definition 7002 Ave. time outside t § (cont.) Delivered condition 3:00 h Setting 0:10 to 100:00 7003 Temp. diff. heating ! Temperature differential for calculating the heating limit. The heating limit defines the value of the outside temperature, below which central heating commences.
  • Page 78: Red.mode T Threshold

    Control settings - system definition 7004 Temp. diff. cooling ! (cont.) The cooling limit defines the value of Menu the outside temperature, above which & "Device settings" cooling mode commences. Similarly & "Programming" to the heating limit, this temperature & "System definition"...
  • Page 79: Primary Pump With Nc

    Control settings - system definition 7006 Frost protection t § (cont.) If the outside temperature drops Menu below this frost protection limit, the & "Device settings" heat pump control unit switches to & "Programming" frost protection mode. Standard mode & "System definition"...
  • Page 80: A Cascade Control

    Control settings - system definition 7008 Swimming pool ! (cont.) Note Menu The thermostat for swimming pool & "Device settings" temperature control is connected to & "Programming" the heat pump control unit via external & "System definition" extension H1. Therefore initially set &...
  • Page 81: B Output Of Lag Heat Pumps

    Control settings - system definition 700B Output of lag heat pumps ! Average output of the lag heat pumps in a cascade, connected via external extension H1. This output information is used by the Menu load manager in the control unit to &...
  • Page 82: External Extension

    Control settings - system definition 7010 External extension ! External extension H1 installed. "Yes" External extension H1 is in- Note stalled and enabled. The functions listed can only be used "No" External extension H1 is if further parameters are set accord- not enabled.
  • Page 83: Op Mode Change Eff

    Control settings - system definition 7011 Op. mode change HC ! (cont.) "10" A1: Heating circuit without Menu mixer & "Device settings" M2: Heating circuit with mixer & "Programming" M3: Heating circuit with mixer, & "System definition" DHW heating & "Op.
  • Page 84: External Demand / Mixer Open

    Control settings - system definition 7013 Op. mode change time ! (cont.) "1" to "12" After this time has expired, the control Duration of the operating mode unit switches back to the operating changeover in hours, starting mode which was enabled before the with the activation of the exter- external changeover.
  • Page 85: External Blocking/Miclose

    Control settings - system definition 7014 External demand / mixer OPEN ! (cont.) "4" M2/M3: Heating circuits with Menu mixer – control mode & "Device settings" Heat demand to the heat pump & "Programming" M2: Heating circuit with mixer – "5"...
  • Page 86: Type Vitosolic

    Control settings - system definition 7015 External blocking/Miclose ! (cont.) M2: Heating circuit with mixer – "2" "7" M2/M3: Heating circuits with mixer – mixer "CLOSED" control mode M3: Heating circuit with mixer – Heat pump blocking mixer "CLOSED" Menu No heat pump blocking &...
  • Page 87: Vitocom 100

    Control settings - system definition 7017 Vitocom 100 ! Using the Vitocom 100 communication interface. The connection is made via KM BUS. & "System definition" & "Vitocom 100" "Yes" Vitocom 100 is installed and enabled. Delivered condition "No" Vitocom 100 is not used. Setting Yes/No Menu...
  • Page 88: A Ext. Blocking Effect

    Control settings - system definition 7019 Priority ext. demand § (cont.) "2" Low priority: Menu As per setting value "0", but & "Device settings" lag heat pumps are also used & "Programming" to generate heat. & "System definition" "3" High priority: &...
  • Page 89: B Wtimer Dhw Circ

    Control settings - system definition 701A Ext. blocking effect ! (cont.) Value Secondary Cylinder Heating Heating Heating cir- pump/ pump circuit circuit cuit pump compres- blocked pump pump A1 blocked blocked blocked blocked "16" "17" "18" "19" "20" "21" "22" "23"...
  • Page 90 Control settings - system definition 701B Wtimer DHW Circ. (cont.) "ON" Menu Appliance operates continu- & "Device settings" ously. & "Programming" Note & "System definition" The connected appliance is stopped & "Wtimer DHW Circ." during DHW cylinder heating. When the auxiliary function ("Auxiliary Delivered condition function", 600B) is enabled, the con- Setting...
  • Page 91: Max. Flow Temp

    Compressor control settings Compressor control settings The control settings for the compressor are explained below. Parameters with the numbers 50xx Note always relate to the first compressor Parameters of the second compressor stage, whereas the numbers 51xx stage are only visible in the control describe the identical parameters of unit if this stage is available and has the second compressor stage.
  • Page 92: Min. Return Temp

    Compressor control settings 5001 Max. flow temp § (cont.) Part number Max. flow temperature Heat pump module Secondary circuit Vitocal 300-G 7284608, 7284609, 60 °C 7284610, 7284611, 7344657, 7283149 Vitocal 300-A 60 °C Menu Delivered condition 60 °C & "Device settings" Setting 25 to 65 °C &...
  • Page 93: Hysteresis Primary

    Compressor control settings 5004 Hysteresis primary § Primary circuit temperature range for starting and stopping the heat pump. The heat pump starts & if the primary inlet temperature exceeds the value "Min. t primary inlet" (5016) by "Hysteresis pri- mary" (5004). &...
  • Page 94: Min. Pause

    Compressor control settings 5005 Min. runtime § (cont.) This function reduces the wear on Menu moving parts of the compressor. The & "Device settings" compressor will only stop after this & "Programming" time has expired. The control unit & "Compressor" uses the signal "Critical draw-off"...
  • Page 95: A Optimum Runtime

    Compressor control settings 5008 Start delay § (cont.) Menu & "Device settings" & "Programming" & "Compressor" & "Start delay" Delivered condition 2:00 min Setting 0:10 to 16:40 A Start signal for heat pump B Primary pump or fan C Secondary pump D Compressor E Start delay F Off...
  • Page 96 Compressor control settings 500A Optimum runtime § (cont.) Brine/water heat pumps Due to the permanent energy extrac- The optimum operating range is the tion in brine/water heat pumps, com- time during which the coefficient of pressor runtimes which are too long performance (COP) over time is can lower the temperature of the almost linear.
  • Page 97: B Defrost Time

    Compressor control settings 500B Defrost time § Max. time for defrosting the evaporator in air/water heat pumps. During the defrost time, the heat Menu pump does not generate any heating & "Device settings" energy. & "Programming" & "Compressor" One of the following conditions must &...
  • Page 98: D Defrost Off Time

    Compressor control settings 500D Defrost OFF time § Blocking time for renewed defrosting of the evaporator in air/water heat pumps. The specified blocking time begins Menu from the end of the last defrost pro- & "Device settings" cess. & "Programming" &...
  • Page 99: F Defrost Start T

    Compressor control settings 500F Defrost start t § Evaporator temperature for the start of the defrost process of air/water heat pumps. The defrost process only starts if the & Temperature differential "Temp. evaporator temperature falls below diff. defrost" (500E) is exceeded. the specified value.
  • Page 100: Dhw With Heat Pump

    Compressor control settings 5011 Max. differential t § (cont.) If this temperature differential Menu exceeds the specified value, the com- & "Device settings" pressor shuts down. & "Programming" & "Compressor" Note & "Max. differential t" The control unit calculates the required temperature values from the Delivered condition pressure values measured at the eva-...
  • Page 101 Compressor control settings 5015 Max. t primary inlet § / 5016 Min. t primary . . . (cont.) The heat pump starts Note & if the primary inlet temperature The fans and compressors in air/ exceeds the value "Min. t primary water heat pumps only start if the inlet"...
  • Page 102: Superheating

    Compressor control settings 5019 Superheating § Suction gas - set superheating temperature. The temperature of the suction gas is Note raised to prevent the compressor Changing the parameters is appropri- drawing in any drops of liquid. This is ate if, for example, refrigerant super- carried out by optimising the expan- heating in the evaporator should be sion valve control and/or by an inter-...
  • Page 103: C Compr.diff.dead Zone

    Compressor control settings 501B EVI hot gas temp. § (cont.) The EVI control circuit uses the Menu injected vapour volume as the & "Device settings" manipulated variable for controlling & "Programming" the hot gas temperature. If the hot gas & "Compressor"...
  • Page 104: E Pwm Cycle Time

    Compressor control settings 501E PWM cycle time § Cycle time for the compressor output control. The output of modulating heat pumps The control unit demands 40% of the is matched through the cyclic change compressor output and the set cycle between compressor delivery and idle time is 20 s.
  • Page 105: Max. Hot Gas Temp

    Compressor control settings 5020 Start open duration § (cont.) The electronic expansion valve open- Menu ing partially over a defined period & "Device settings" ensures an adequate supply of refrig- & "Programming" erant to the compressor. This is parti- & "Compressor"...
  • Page 106: High P Dead Zone

    Compressor control settings 5022 Max. high pressure § (cont.) Delivered condition 27.7 bar(a) & "Compressor" Setting 10 to 50 bar(a) & "Max. high pressure" 5023 High p dead zone § Dead zone around upper condensation pressure limit. After a high pressure shutdown, the Menu compressor does not restart until the &...
  • Page 107: Low Pressure Limit

    Compressor control settings 5025 Low pressure limit § Suction gas - lower pressure limit (low pressure limit). If the suction gas pressure falls below Menu the specified value, the compressor & "Device settings" shuts down (low pressure shutdown). & "Programming" In the delivered condition, different &...
  • Page 108: Output

    Compressor control settings 5027 Low pressure delay § (cont.) In some heat pump operating states, & Start and end of the defrost process such as the compressor start phase, for air/water heat pumps the suction gas pressure often briefly falls below the lower limit. This is sup- Menu pressed within the specified delay so &...
  • Page 109: Number Of Heat Pumps

    Compressor control settings 5030 Output ! (cont.) Delivered condition 10 kW Menu Setting 1 to 255 kW & "Device settings" & "Programming" & "Compressor" & "Output" 5707 Number of heat pumps ! Heat pump number in a cascade via LON. The heat pumps within a cascade via Menu LON must be uniquely identifiable for...
  • Page 110: B00 Ext. Heat Source

    External heat source control settings 7B00 Ext. heat source ! Enabling external heat sources. If there is a corresponding heat & "Ext. heat source" demand, the external heat source can & "Ext. heat source" be additionally started by the control unit.
  • Page 111: B03 Threshold

    External heat source control settings 7B02 Dual-mode temperature ! (cont.) If the long-term average outside tem- Menu perature falls below the dual-mode & "Device settings" temperature, the control unit enables & "Programming" operation of the external heat source. & "Ext. heat source" Requirement: Parameter "Ext.
  • Page 112: B04 Delay

    External heat source control settings 7B03 Threshold § (cont.) Setting 10 to 30000 K∙min 7B04 Delay § Start delay for the external heat source. The external heat source does not Menu start within the specified period fol- & "Device settings" lowing matching of the set flow tem- &...
  • Page 113: B07 Runtime Without Demand

    External heat source control settings 7B06 Min. runtime § (cont.) The external heat source does not Menu stop during this period. The control & "Device settings" unit cannot reset the demand signal & "Programming" until the minimum runtime has & "Ext.
  • Page 114: B09 Mixer Active Zone § / 7B0A Mixer Dead Zone

    External heat source control settings 7B08 Mixer runtime § (cont.) Setting 0:05 to 4:15 7B09 Mixer active zone § / 7B0A Mixer dead zone § External heat source - mixer active zone/dead zone. The dead zone (switching point inter- Menu val) determines the fluctuation range &...
  • Page 115: B0D Ext. Hs For Dhw

    External heat source control settings 7B0D Ext. HS for DHW ! Using the external heat source for DHW heating. "Yes" External heat source is en- & "Ext. heat source" abled for DHW heating. & "Ext. HS for DHW" "No" External heat source is blocked for DHW heating.
  • Page 116: Dhw Control Settings 6000 Set Dhw Temp

    DHW control settings 6000 Set DHW temp. DHW cylinder set temperature for DHW heating. If the heat pump alone cannot achieve Menu the set DHW temperature, the instan- & "Device settings" taneous heating water heater, immer- & "Programming" sion heater or an external heat source &...
  • Page 117: Min. Temperature

    DHW control settings 6004 Operating mode § Mode to select the operating mode for DHW heating. "Standby" The operating mode depends No operating mode can be set, only frost protection. & Operating mode selector "Switching times" & External operating mode The operating mode is only se- changeover lected via the programmed...
  • Page 118: Max. Temp

    DHW control settings 6005 Min. temperature ! (cont.) This set temperature is used as the Note frost protection limit for the DHW Brine/water heat pumps of type BWC cylinder in "OFF" operating mode. use the integral three-way diverter DHW is heated if the temperature falls valve "Central/DHW heating"...
  • Page 119: Hysteresis ! / 6008 Hyst. Booster Heater

    DHW control settings 6007 Hysteresis ! / 6008 Hyst. booster heater ! Cylinder temperature hysteresis for starting and stopping DHW heating. The set value determines the devia- Note tion from the set DHW cylinder tem- The value selected for "Hysteresis" perature ("Set DHW temp.", 6000) at should be higher than the expected which DHW heating is started and...
  • Page 120: Start Optimisation

    DHW control settings 6009 Start optimisation Comfort function for DHW cylinder heating. The start optimisation ensures that Note DHW is already available at the If a second, lower temperature sensor required temperature at the beginning is installed in the DHW cylinder, heat- of DHW heating in accordance with ing with start optimisation is started the set switching times.
  • Page 121: B Auxiliary Function

    DHW control settings 600B Auxiliary function Auxiliary DHW heat-up function to kill bacteria. At the first cylinder heating every Note Monday, the total cylinder content is To prevent the cylinder content mixing heated to the "Set temp. 2" (600C). with the DHW circuit during DHW In order that bacteria are also killed in cylinder heat-up, the control unit does the DHW circulation line, the DHW cir-...
  • Page 122: E Second Temperature Sensor

    DHW control settings 600D T rise / hour § Temperature rise per hour during DHW heating. This parameter is used for two func- & Start and stop optimisation for tions: DHW heating & Starting booster heaters for DHW This parameter specifies the tem- heating perature rise for calculating the If the temperature rise during DHW...
  • Page 123: F Excess Reaction

    DHW control settings 600E Second temperature sensor ! (cont.) Delivered condition Menu Setting Yes/No & "Device settings" & "Programming" & "DHW" & "Second temperature sensor" 600F Excess reaction § Heat drawn off by the DHW cylinder when the heat pump produces an excess of heat or the heat drawn by the secondary circuit is suddenly choked off.
  • Page 124: Max. Runtime

    DHW control settings 6010 DHW priority § (cont.) Delivered condition Setting Yes/No 6011 Max. runtime § Maximum duration of DHW heating with simultaneous heat demand from the heating circuits, if "DHW priority" is set to "Yes". If the heating circuits do not require Menu any heating for the heating circuit, the &...
  • Page 125: Dhw With E Heating

    DHW control settings 6014 Booster heaters ! (cont.) "No" DHW is only heated by the If the set cylinder temperature cannot heat pump if it is enabled be reached with the heat pump during for this via parameter DHW heating, either the immersion "DHW with heat pump"...
  • Page 126: Electric Heating

    Electric heater control settings 7900 Inst.htg.water heat ! Instantaneous heating water heater installed. If an instantaneous heating water Menu heater is installed in the heating water & "Device settings" flow, it must be enabled for use. & "Programming" & "Electric heating" "Yes"...
  • Page 127: Heater Rod Delay

    Electric heater control settings 7902 Electric heating (cont.) Note Menu Even if the instantaneous heating & "Device settings" water heater is blocked for heating & "Programming" mode, it is started by the control unit & "Electric heating" for frost protection of the heating sys- &...
  • Page 128: Max. Stage E Heating

    Electric heater control settings 7905 Heater rod delay § (cont.) Within the given period, the instanta- Note neous heating water heater does not The control unit only starts the electric start after a change from "Standard"/ booster heaters within the specified "Reduced"...
  • Page 129: Stage Power Failure

    Electric heater control settings 7908 Blocking time, power failure § (cont.) This time prevents the instantaneous Menu heating water heater starting prema- & "Device settings" turely, after the heat pump has been & "Programming" shut down for a prolonged period. &...
  • Page 130 Electric heater control settings 790A Stage at power-OFF ! (cont.) "3" Output stage 3, or subject to The selected stage and all those type and power connection, below it will be enabled. stage 1 and 2 simultaneously, e.g. 9 kW "0"...
  • Page 131: Hp For Dry. Buildings

    Control settings - internal hydraulics 7300 HP for dry. buildings ! Using the heat pump for drying buildings. Heat pumps are not designed for a Note very high energy demand, e.g. for dry- Drying buildings with an instanta- ing buildings. Furthermore, the heat neous heating water heater results in pump primary circuit is often not yet high power consumption.
  • Page 132 Control settings - internal hydraulics 7303 Screed program ! (cont.) "0" "3" No temperature/time profile Temperature/time profile 3 (to Termination of the current profile ÖNORM) and operation continued in heat- ing or cooling mode. "1" Temperature/time profile 1 (in acc. with EN 1264-4) A Flow temperature B Days "4"...
  • Page 133: Hysteresis Secondary

    Control settings - internal hydraulics 7303 Screed program ! (cont.) "6" "12" Temperature/time profile 6 Fixed value temperature pro- gram Duration: 30 days Note For screed drying, observe the speci- fications of EN 1264-4 for underfloor heating systems. Screed drying with an instantaneous heating water heater results in high power consumption.
  • Page 134: Integral 3-Way Valve

    Control settings - internal hydraulics 7304 Hysteresis secondary § (cont.) The secondary circuit set temperature Menu results accordingly from the current & "Device settings" heat demands. The hysteresis of the & "Programming" secondary circuit temperature speci- & "Internal hydraulics" fies the deviation from the set return &...
  • Page 135: Prop. 3-Way Valve

    Control settings - internal hydraulics 7306 Prop. 3-way valve § Proportion of the mixer control circuit "Central heating/DHW" (three-way diver- ter valve). Note Menu Brine/water heat pumps of type BWC & "Device settings" use the integral three-way diverter & "Programming" valve with a stepper motor as a mixer.
  • Page 136: Heat P Night Op

    Control settings - internal hydraulics 7308 Heat p night op § Operating mode of air/water heat pumps during the night. Alongside output regulated mode, a Menu quieter mode with constant, reduced & "Device settings" fan speed is available for air/water &...
  • Page 137: C Set Flow Ex. Demand

    Control settings - internal hydraulics 730B Sec pump run-on § (cont.) After heat generation has ended, par- Menu ticularly for DHW heating, heat is still & "Device settings" available at the condenser. During the & "Programming" run-on time, the secondary pump &...
  • Page 138: E E Heating Threshold

    Control settings - internal hydraulics 730D Heat/DHW diverter v § (cont.) -Vitocal 300-G Menu -Vitocal 300-A, type & "Device settings" AW-O & "Programming" -Vitocal 300-A, type & "Internal hydraulics" AWC-I & "Heat/DHW diverter v" Setting Yes/No Delivered condition 730E E heating threshold § Start criteria for instantaneous heating water heater.
  • Page 139 Control settings - heating water buffer cylinder 7200 Buffer cylinder ! Heating water buffer cylinder or low loss header are installed. If a heating water buffer cylinder is Menu installed as an option with system dia- & "Device settings" grams 1 and 2, the buffer is enabled &...
  • Page 140: Hysteresis

    Control settings - heating water buffer cylinder 7201 Switch t buffer cyl. (cont.) Setting OFF / & "Buffer cylinder" Reduced / & "Switch t buffer cyl." Standard / Fixed value Delivered condition Standard 7202 Fixed temp. ! Set temperature for "Fixed value" operating mode of the heating water buffer cylinder.
  • Page 141: Stop Optimisation

    Control settings - heating water buffer cylinder 7203 Hysteresis ! (cont.) Note Menu When using a low loss header, enter a & "Device settings" higher value than for hysteresis of the & "Programming" secondary circuit ("Hysteresis sec- & "Buffer cylinder" ondary", 7304).
  • Page 142: Excess Reaction

    Control settings - heating water buffer cylinder 7205 Stop optimisation § (cont.) Delivered condition & "Buffer cylinder" Setting Yes/No & "Stop optimisation" 7206 Excess reaction § Heat drawn off by the heating water buffer cylinder when the heat pump pro- duces an excess of heat or the heat drawn by the secondary circuit is suddenly choked off.
  • Page 143: Room T Standard / 2001 Room T Reduced

    Heating circuit control settings Heating circuit control settings The control settings for the heating circuits are explained below. Parameters with numbers 2xxx Mixer circuit 2 with KM 4xxx always relate to the first heating cir- BUS mixer cuit (A1), whereas numbers 3xxx and 4xxx describe the identical para- Note meters of the second (M2) and third...
  • Page 144 Heating circuit control settings 2000 Room t standard / 2001 Room t reduced (cont.) Room t standard Room t reduced Delivered condition 20 °C Delivered condition 16 °C Setting 10 to 30 °C Setting 10 to 30 °C 2002 Switching times HC Time program for the heating circuits.
  • Page 145: Operating Mode

    Heating circuit control settings 2003 Remote control ! Remote control installed. A separate Vitotrol 200 remote control Note unit can be used for each heating cir- Remote control units have no function cuit. when the heat pump is in manual mode "h".
  • Page 146: Room Control

    Heating circuit control settings 2004 Operating mode § (cont.) "Switching times" Note The operating mode is only se- If all functions of the programming unit lected via the programmed are to be used, select the "Standard" switching times, independent of setting for this parameter.
  • Page 147: Heating Curve Level / 2007 Heating Curve Slope

    Heating circuit control settings 2005 Room control § (cont.) "Yes" Room temperature-depen- "No" Weather-compensated dent control enabled. In control enabled. The con- contrast to weather-com- trol unit uses the current pensated control, the con- level and slope of the heat- trol unit does not use the ing curve to calculate the level and slope of the heat-...
  • Page 148: Integral Room Thermostat

    Heating circuit control settings 2009 Integral room thermostat § Integral proportion of the control circuit for room temperature-dependent heat- ing mode. A high value results in a rapid & "Heating circuits" response. Requirement: "Room con- & "Integral room temperature con- trol"...
  • Page 149: D Max. Flow Corr

    Heating circuit control settings 200B Room t hook-up ! (cont.) "1" Weather-compensated control Menu with room influence only for & "Device settings" "Standard" operating mode. & "Programming" "2" Weather-compensated control & "Heating circuits" with room influence only for & "Room t hook-up" "Reduced"...
  • Page 150: Dhw For Party

    Heating circuit control settings 200E Max. flow temp. ! (cont.) If a higher value than given here Note results due to outside temperature Since the heat pump control unit only and heating curve, the control unit limits the set value with this para- selects the value specified here as meter, always protect underfloor heat- the maximum.
  • Page 151: Room T Excess

    Heating circuit control settings 2011 Excess reaction § (cont.) "0" No heat drawn off. Note "1" Heat will be drawn off only in If the heat drawn off in case of excess case of a critical excess, i.e. if is also intended for other consumers, critical temperatures are the load manager inside the control reached in the heat pump re-...
  • Page 152: Mixer Runtime

    Heating circuit control settings 2014 Flow t excess § (cont.) The set flow temperature in the sec- Menu ondary circuit corresponds to the & "Device settings" highest set flow temperature in one of & "Programming" the heating circuits. To compensate &...
  • Page 153 Heating circuit control settings 2018 Mixer active zone § / 2019 Mixer dead zone . . . (cont.) Active zone Menu Delivered condition & "Device settings" Setting 2 to 40 K & "Programming" & "Heating circuits" Dead zone & "Mixer active zone" or "Mixer Delivered condition dead zone"...
  • Page 154: Cooling Circuit

    Cooling control settings 7100 Cooling ! Type of cooling mode. "0" No cooling. Menu "1" "Natural cooling" & "Device settings" Direct cooling of a heating or & "Programming" cooling circuit using the NC- & "Cooling" Box without mixer. & "Cooling" "2"...
  • Page 155: Room Temperature

    Cooling control settings 7102 Room temperature Set room temperature for the separate cooling circuit. Requirement: Room temperature sen- Note sor is enabled (parameter "Remote For cooling a heating circuit, the con- control", 2003 set to "Yes"), para- trol unit uses the set room tempera- meter "Room control"...
  • Page 156: Room T Hook-Up Slope

    Cooling control settings 7104 Room t hook-up slope ! Level of the room influence (room temperature hook-up slope). This value specifies the influence of Note room temperature hook-up on the set Room influence has an effect both for flow temperature with weather-com- cooling mode on one heating circuit pensated cooling mode.
  • Page 157: Ranking Rts

    Cooling control settings 7106 Ranking RTS § Switching the room temperature sensor for cooling mode to a separate cooling circuit. This value determines which room If the heating circuit and separate temperature sensor is used for room cooling circuit affect the same room, temperature-dependent control of the using the heating circuit room tem- separate cooling circuit.
  • Page 158: Cooling Curve Level ! / 7111 Cooling Curve Slope

    Cooling control settings 7108 Integral room thermostat § (cont.) A high value results in a rapid Menu response. Requirement: "Room con- & "Device settings" trol" (parameter 7105) is set to & "Programming" "Yes". & "Cooling" & "Integral room temperature con- Note troller"...
  • Page 159: Nc Mixer Type

    Cooling control settings 7115 NC mixer type § Control of the NC-Box mixer motor. "0" Via KM BUS. Menu "1" Directly via heat pump control & "Device settings" unit. & "Programming" "2" No NC mixer control; heating & "Cooling" circuit mixer is used to set the &...
  • Page 160: Lon Module Installed

    The & "Communication" first part is permanently set to the & "Subscriber number" or "System same value for all Viessmann appli- number" ances. The other parts comprise sys- tem and subscriber number. This Subscriber number enables the subscribers to be...
  • Page 161: Fault Manager

    Communication control settings 7779 Fault manager ! Device is fault manager within a system. This parameter determines whether Menu the device should collect and display & "Device settings" all system fault messages. Further- & "Programming" more, the control unit monitors all &...
  • Page 162: C Receive Heartbeat

    Communication control settings 779C Receive heartbeat ! Receive interval for the values and messages transmitted via LON. If no signal is received for a size or Menu message within this cycle time, the & "Device settings" control unit sets this value or status to &...
  • Page 163: C00 Auto. Su/W. Time

    Time control settings 7C00 Auto. su/w. time ! Automatic summer/wintertime changeover. In the delivered condition, the chan- "Yes" Automatic changeover en- geover will always take place in the abled. night from Saturday to Sunday on the "No" Automatic changeover not last weekend in March and October.
  • Page 164: C03 Summertime - Day

    Time control settings 7C02 Summertime - week ! (cont.) "1" to "4" Menu Week number, going up from & "Device settings" the first week in the month. & "Programming" First to fourth week. & "Time" "5" Last week of month. &...
  • Page 165: C04 Wintertime - Month

    Time control settings 7C04 Wintertime - month ! Month to change over to wintertime. Menu Delivered condition & "Device settings" Setting 1 to 12 & "Programming" & "Time" & "Wintertime - month" 7C05 Wintertime - week ! Week to change over to wintertime. "1"...
  • Page 166: C06 Wintertime - Day

    Time control settings 7C06 Wintertime - day ! Weekday to change over to wintertime. Menu Delivered condition & "Device settings" Setting 1 to 7 & "Programming" & "Time" & "Wintertime - day"...
  • Page 167: Keyword Index

    Keyword index Keyword index Access code 9, 10 Cascade ..............Access protocol Cascade .
  • Page 168 Keyword index Keyword index (cont.) Cooling limit & Temperature differential for Dead zone 114, 152 ......calculation Dead zone .
  • Page 169 Keyword index Keyword index (cont.) DHW heating & Auxiliary function 22, 121 EEV controller 13, 59 ........&...
  • Page 170 Keyword index Keyword index (cont.) Externally changing operating modes & Assigning system components Heat pump . . . & Number ........Heating circuit .
  • Page 171 Keyword index Keyword index (cont.) Hot gas temperature & Maximum Lag heat pumps ....... . .
  • Page 172 Keyword index Keyword index (cont.) Max. superheating temperature Natural cooling ......& Suction gas NC-Box mixer control .
  • Page 173 Keyword index Keyword index (cont.) Refrigerant circuit Screed program ..........Refrigerant circuit Second temperature sensor .
  • Page 174 Keyword index Keyword index (cont.) Start threshold & External heat source Temperature differential defrost ....& Instantaneous water heater Temperature limit .
  • Page 176 Applicability WPR 300 heat pump control unit Vitocal 300-G Vitocal 300-A Viessmann Werke GmbH&Co KG Viessmann Limited D-35107 Allendorf Hortonwood 30, Telford Telephone: +49 6452 70-0 Shropshire, TF1 7YP, GB Fax: +49 6452 70-2780 Telephone: +44 1952 675000 www.viessmann.com Fax: +44 1952 675040...

Table of Contents