Control settings - system definition

7010 External extension !

External extension H1 installed.
"Yes"
External extension H1 is in-
stalled and enabled.
"No"
External extension H1 is
not enabled.
External extension H1 can be used for
one of the following functions:
&
Swimming pool water heating
&
Heat pump cascade
&
External operating mode change-
over
&
External demand
&
External mixer OPEN
&
External blocking
&
External mixer CLOSE

7011 Op. mode change HC !

Assigning external operating mode changeover via signal "External demand /
mixer OPEN".
This parameter specifies which sys-
tem components the external operat-
ing mode changeover will affect. With
the external operating mode change-
over, a heating circuit with mixer for
example can be switched via a remote
monitoring system from "Reduced" to
"Standard" operating mode.
"0"
DHW heating
"1"
A1: Heating circuit without
mixer
"2"
A1: Heating circuit without
mixer, DHW heating
"3"
M2: Heating circuit with mixer
"4"
M2: Heating circuit with mixer,
DHW heating
82
Note
The functions listed can only be used
if further parameters are set accord-
ingly.
Menu
&
"Device settings"
&
"Programming"
&
"System definition"
&
"External extension"
Delivered condition
Setting
"5"
A1: Heating circuit without
mixer
M2: Heating circuit with mixer
"6"
A1: Heating circuit without
mixer
M2: Heating circuit with mixer,
DHW heating
"7"
M2: Heating circuit with mixer
M3: Heating circuit with mixer
"8"
M2: Heating circuit with mixer
M3: Heating circuit with mixer,
DHW heating
"9"
A1: Heating circuit without
mixer
M2: Heating circuit with mixer
M3: Heating circuit with mixer
No
Yes/No