7779 Fault manager !

Device is fault manager within a system.
This parameter determines whether
the device should collect and display
all system fault messages. Further-
more, the control unit monitors all
subscribers for failure and generates
central fault messages.
"Yes"
Device is fault manager.
"No"
Device is not fault manager.
Note
Only one device may be configured as
fault manager within a system. Excep-
tion: The Vitocom remote monitoring
systems may also be fault managers.

7797 Outside temperature !

Transmit/receive the current outside temperature within a system.
If several subscribers use the current
outside temperature value, this can
be made available centrally by one
device within a system. All other sub-
scribers in the same system can
receive the temperature values.
"0"
Device captures the outside
temperature via the locally con-
nected temperature sensor.
"1"
Device captures outside tem-
perature of another LON sub-
scriber within the same system.
"2"
Device transmits outside tem-
perature. All LON subscribers
within the same system can re-
ceive the values.
Communication control settings
Menu
&
"Device settings"
&
"Programming"
&
"Communication"
&
"Fault manager"
Delivered condition
Setting
Note
Only one of the subscribers within a
system may transmit the outside tem-
perature.
Menu
&
"Device settings"
&
"Programming"
&
"Communication"
&
"Outside temperature"
Delivered condition
Setting
No
Yes/No
0
0 / 1 / 2
161