Independent mA Setpoints (P210 and P211)

Use these features to reference the minimum and/or maximum mA output to any point in
the measurement range.
P201—mA
Function Settings
Level, Space, or Distance
Volume
Volume Rate
mA input or
Communications Input
P210 0/4 mA Output Setpoint
Sets the process level corresponding to the 0 or 4mA value.
Primary Index
Values
Related
Enter the value (in applicable units or %) to correspond to 0 or 4 mA.
P211 20 mA Output Setpoint
Sets the process level that corresponds to the 20 mA value.
Primary Index
Values
Related
Enter the value (in applicable units or %) to correspond to 20 mA.

mA Output Limits (P212 and P213)

Use these features to adjust the minimum and/or maximum mA output values, which
should suit the input limit requirements of the external device.
P212 mA Output Min Limit
Sets the minimum mA output value (in mA) to be produced.
Primary Index
Values
Related
Page 48
Enter the material level in Units (P005) or percent of Span
(P007) as referenced to Empty (P006).
Enter the volume in Max Volume (P051) units or as a per-
cent of Max Volume.
Enter the volume rate in volume/min. Ensure the % symbol
is displayed before attempting to enter a % value.
Not Applicable
mA output
Range: -999 to 9999
P211 20 mA Output Setpoint
mA output
Range: -999 to 9999
P210 0/4 mA Output Setpoint
mA output
Range: 0.000 to 22.00
Preset: 0.0 or 3.8
P200 mA Output Range
P213 mA Output Max Limit