P819 Profile Pointer Amplitude
The amplitude (in dB above 1 μV) of the Echo Profile at the Pointer position.
Values
Related
P820 Algorithm
Chooses the algorithm to generate the measured value from the profile.
Values
Related
Use this to select the algorithm(s) the Sonic Intelligence echo selection is based on. Use
P805 Echo Confidence (page 69) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm, either by entering the numeric
value desired, or as below:
1.
Press MEASURE
2.
Press ARROWS
3.
Press ENTER
7ML19985BE02
Range: 00 to 99 (view only)
P817 Profile Pointer Time
P818 Profile Pointer Distance
P820 Algorithm
P821 Spike Filter
P822 Narrow Echo Filter
P823 Reform Echo
P825 Echo Marker Trigger
ALF = long range Area, Largest, and First average (general pur-
1
pose, solids)
2
A = long range Area only (coarse, heaped solids)
3
L = long range Largest only (liquids, open vessels)
4
F = long range First only (liquids, closed vessel)
5
AL = long range Area and Largest average (fine heaped solids)
6
AF = long range Area and First average (coarse flat solids)
LF = long range Largest and First average (general purpose,
7
liquids)
8
* bLF = short range Largest or First (general purpose)
9
bL = short range Largest only (solids and open vessel liquids)
10
bF = short range First only (closed vessel liquids)
P805 Echo Confidence
P817 Profile Pointer Time
P818 Profile Pointer Distance
P819 Profile Pointer Amplitude
P821 Spike Filter
P822 Narrow Echo Filter
P823 Reform Echo
P825 Echo Marker Trigger
to display the Auxiliary Function symbol.
to access the desired Reading display symbols.
when the required algorithm is displayed.