Interconnection

Before interconnecting system components to the SITRANS LU01 terminals, verify all
components have been installed in accordance with the associated product instruction
manuals.
Connect all associated equipment cable shields to the SITRANS LU01 shield connections.
To avoid differential ground potentials, do not connect cable shields to ground (earth)
elsewhere. Insulate or tape cable shields at all shield junctions to prevent ground loops.
AC Model
BIPOLAR
RS-232
RS-485
TERM INATIO N
RJ-11
communication
mode LED
NORM/TRIP
switch
terminal block
RJ-11 port
WARNINGS:
•All field wiring must have insulation suitable for at least 250V.
•Hazardous voltage present on transducer terminals during operation
•Relay contact terminals are for use with equipment having no accessible
live parts and wiring having insulation suitable for at least 250V.
7ML19985BE02
display
G ND
SCO PE SYN C
TP4
TP 6
TP 5
NORM
TRIP
TB1
1
2
3
4
5
6
7
8
9
+
-
+
-
1
2
mA
1
2
OUTPUTS
!
!
SITRANS LU01 – INSTRUCTION MANUAL
optional
scope
SmartLinx
connections
module
10 11 12 13 14 15
16 17 18 19 20 21 22 23
24 25
26
2
1
2
3
4
1
RELAYS
RELAYS SHOWN IN
DE-ENERGIZED POSITION
250
V
5AMP
SEE INSTRUCTION BOOK
FOR COMPLETE RATING
board B
EPROM
board A
U31
voltage
select
200V
115V
OFF
100V
27 28 29 30 31 32 33
34
35
36 37
1
2
1
2
L2/N L1
BIPOLAR CURRENT LOOP
RS-232
POSITION SW1 FOR
100/115/200/230
V
OPERATION
RS-485
[ 50/60 HZ 31VA ]
Page 11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents