Rp7517 Electronic-Pneumatic Transducer; Electronic-Pneumatic - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

Pneumatic Transducer

RP7517 Electronic-Pneumatic Transducer

Dimensions in inches (millimeters)
2-7/16 (62)
2 (51)
1-1/2
(39)
MODEL WITH COVER
2-7/16 (62)
2 (51)
1
MODEL WITHOUT COVER
1
2 TERMINALS ON RP7517A1017
3 TERMINALS ON RP7517B1024
Electrical
Product Number
Connections
RP7517A1009
30 in. (762 mm)
lead wire
RP7517A1017
screw terminals
for 14 to 22 gage
wire
RP7517B1016
30 in. (762 mm)
lead wire
RP7517B1024
screw terminals
for 14 to 22 gage
wire
30
customer.honeywell.com
2 (51)
3-5/8
(92)
1-7/8 (48)
3-3/8
(86)
M13904
Power
Input Signal
Consumption Voltage
2 to 10 Vdc
16mA at 12 Vdc Powered by
2 to 10 Vdc
16mA at 12 Vdc Powered by
2 to 10 Vdc at
1.7 vA
0.1 mA max
2 to 10 Vdc at
1.7 vA
0.1 mA max
Electronic-Pneumatic Transducers are used in electronic-
pneumatic control systems to convert a proportional electric
output signal from a controller into a direct-acting, proportional
pneumatic signal.
Screw mounting or snap rail (models with cover).
Factory calibrated.
Dual barb fittings.
High accuracy.
RP7517 Typical Piping/Wiring
EXCEL
PANEL
M
I/O
B
C
RP7517B
O
P
A
U
R
D
Application: Electric to pneumatic Transducer
Action: Direct Acting
Airflow Usage: 0.025 scfm (117mL/s)
Connections: Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic
tubing
Maximum Operating Temperature:
Maximum Operating Pressure: 30 psi (205 kPa)
Pressure Ranges: 0 to 18 psi (0 to 125 kPa)
Nominal High End: 16 psi with 18 psi main pressure at 12 Vdc
(110 kPa with 125 kPa main pressure at 12 Vdc)
Nominal Low End: 0.5 psi at 0 Vdc (3.5 kPa at 0 Vdc)
Output Pressure Range: 3 to 15 psi (21 to 103 kPa)
Capacity: 0.45 scfm (211 mL/s)
Humidity Ratings: 5 to 95% RH
Description
Electronic Pneumatic Transducer with direct
Control
action and 2 to 10 vdc input signal. Powered
signal
by control signal.
Electronic Pneumatic Transducer with direct
Control
action and 2 to 10 vdc input signal. Powered
signal
by control signal
24 Vac
Electronic Pneumatic Transducer with direct
external
action and 2 to 10 Vdc at 0.1 mA max input
transformer
signal. External transformer required.
24 Vac
Electronic Pneumatic Transducer with direct
external
action and 2 to 10 Vdc at 0.1 mA max input
transformer
signal. External transformer required.
70-6925
HEATING
COIL
SUPPLY
AIR
DUCT
TEMP
SENSOR
N.O.
VALVE
M5431
131 F (55 C)
Includes
With cover, without
internal power supply
(2-wire)
Without cover, without
internal power supply for
panel mounting (2 wire)
With cover, external
transformer required, 24
Vac, 50/60 Hz, (3 wire)
Without cover, external
transformer required, 24
Vac, 50/60 Hz, (3 wire)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents