Tp970 Pneumatic Thermostat - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

TP970 Pneumatic Thermostat

Typical Standard Throttling Range Piping
TP970A,B OR
TP9600A,B
M B
M
N.O.
SUPPLY
C3535-1
Application Type: Heating
Dimensions, Approximate: 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
(83 mm high x 51 mm wide x 41 mm deep)
Airflow Usage: 0.011 scfm (5.2 mL/s)
Mounting: Wall
Operating Temperature: 100 F maximum
Storage Temperature: 150 F maximum (66 C maximum)
Remote Bulb: No
Sensor Element: Bimetal
Setpoint: Single
Number of Pipes: 2
Maximum Operating Pressure: 25 psi (170 kPa)
Accessories:
14004439-001 Setpoint Extension
14002430-001 Thermostat Guard
14002362-001 Duct Sampling Chamber
14003192-001 Wallplate adapter kit. Adapts HP970 or TP970 series
stats to HP900 and TP900 flush mounted and TP910 series flush or
surface mounted installations
14004447-001 Setpoint Cam Assembly for TP970A1004, A1012,
A1020, A1038, A1046, A1053, A1095, A2004, A2012, A2020, A2038,
A2053, A2095; TP970C; TP972A1143, A2143; TP973A1001, A1019,
A1127
14004447-002 Setpoint Cam Assembly for TP970B1002, B1010,
B1028, B1036, B2002, B2010, B2028, B2036; TP970D;
Two-pipe, single setpoint, pneumatic thermostat used to provide
proportional control of pneumatic valves and damper actuators in
heating and air conditioning systems. Replacement kits are
available for Johnson, Powers, Robertshaw, Barber-Colman, and
older Honeywell two-pipe pneumatic thermostats.
Honeywell's best pneumatic thermostat-TP970 series.
Shock-resistant, suspension-mounted thermostats provide
dependable performance and responsiveness year in and year out.
Pilot operated for high capacity.
Direct Acting (DA) and Reverse Acting (RA) models are available.
Wide throttling range models for Zero Energy Band (ZEB) operation
are available.
Adapter plate in Convertastat and Modernization kits covers existing
thermostat wallmark.
Backplate has molded air connections-no separate fittings needed.
Universal locking cover with satin chrome finish and horizontal,
vertical, or blank window options.
Typical Wide Throttling Range Application.
Typical Wide Throttling Range Piping
M
HEATING
VALVE
2 TO 5 PSI
(14 TO 34 kPa)
N.O.
SPRING
VALVE
OPEN
4 DEGREES F
(2.2 DEGREES C)
ZERO
ENERGY
BAND
VALVE
CLOSED
66F
68F
70F
20C
THERMOSTAT SETTING
TR=10 DEGREES F
(5.6 DEGREES C)
TP972A1002, A1010, A1028, A1044, A2002, A2010, A2028, A2044;
TP973B1009, B1017, B1025, B1108
14004447-005 Setpoint Cam Assembly for TP970B1044; TP972A1051,
A1101
305965 1-1/2 in. diameter, 1/8 NPT center stem back mount Pressure
Indicating gauge (0 to 30 psi scale) with +/- 4% accuracy
AK3863 Honeywell Thermostat Tool Kit, TP970/TP900
CCT729A Gauge Adapter for Calibration. Add 305965 0 to 30 psi
gauge for Complete Tool.
CCT735A Thermostat Calibration Tool includes Allen wrench for cover
installation.
Replacement Parts:
14001865-001 Filter Cartridge Assembly
14002053-001 Back Plate Assembly
14002374-004 Restrictor Block Assembly,.005 in., For TP970A-D;
TP971A-E except C; TP972A; TP973A-B; TP9600 family; HP970A-B;
and HP972B
14002573-001 Modernization Kit to convert all 1 & 2 pipe Honeywell &
competitive pneumatic stats to TP970, TP971A, TP972, TP973,
TP974, TP9600 family; HP970, HP971 and HP972
14004459-001 Repair kit consisting of a thermometer assembly, a
thermometer post and a 60 to 90F Aluminum Scaleplate
14004460-001 Nozzle, Throttling Plate and Bimetal Assembly, DA, Left
side
70-6925
Thermostats
TP970C
DIRECT
ACTING
M B
COOLING
VALVE
9 TO 13 PSI
(62 TO 90 kPa)
N.C.
SPRING
72F
74F
76F
78F
24C
22C
C3538
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents