Lp915 Pneumatic Temperature Sensor - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

Temperature Sensors

LP915 Pneumatic Temperature Sensor

LP915A Typical Piping Duct-Mounted Application
4
8
9
2
3
1
VALVE
M
Number of
Product Number
Pipes
LP915A1044
1
LP915A1051
1
LP915A1077
1
48
customer.honeywell.com
7
5
6
RP920
LP915A
M5566
Element Length
Sensor Element
(ft)
Liquid-filled
18 1/2 ft
Liquid-filled
8 7/8 ft
Liquid-filled
18 1/2 ft
One-pipe, direct-acting temperature sensor used with RP908/
RP920 Controllers to provide proportional control of pneumatic
valve or damper actuators. Averaging, liquid-filled element for
duct mounting.
Easily formed into variety of configurations to assure sensing of
average temperatures.
Continuous temperature indication available by using receiver gage.
Application Type: Temperature Sensor
Dimensions, Approximate: 3 in. high x 1 7/8 in. wide x 1 1/2 in. deep
(76 mm high x 44 mm wide x 33 mm deep)
Action: Direct Acting
Airflow Usage: 0.019 scfm (540 sccm)
Connections: Push-on barb for 5/32 in. (4 mm) and 1/4 in. (6 mm) O.D.
tubing
Maximum Operating Temperature:
Maximum Operating Pressure:
Output Pressure Range: 3 psi to 15 psi (21 kPa to 103 kPa)
Supply Pressure: 18 psi (124 kPa)
Accessories:
314439 Duct Mounting Clip for Averaging capillary
Temperature Sensing Range
(m)
(F)
5.6m
0 F to 200 F
2.7m
0 F to 200 F
5.6m
25 F to 125 F
70-6925
225 F (118 C)
25 psi (172 kPa)
(C)
Mounting
-18 C to +93 C
Duct mount
-18 C to +93 C
Duct mount
-4 C to +52 C
Duct mount

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents