Honeywell Pneumatic Controls Engineering Manual page 15

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

Application Type: Unit Ventilator
Dimensions, Approximate: 4 3/4 in. high x 3 3/4 in. wide x 3 in. deep
(121 mm high x 95 mm wide x 76 mm deep)
Airflow Usage: 0.022 scfm (10.4 mL/s) with 0.007 in. restriction
Air Connections: Barb fittings 1/4 in. (6 mm)
Mounting: In compartment of a unit ventilator
Operating Temperature: 135 F maximum (57 C maximum)
Storage Temperature: 150 F maximum (66 C maximum)
Remote Bulb: Yes
Sensor Element: Bulb 1/2 x 5 7/8 in., capillary 36 in. (914 mm) long
Setpoint: Single
Number of Pipes: 2
Product Number
Action
Sensor Element
LP916A1019
Direct
Bulb 1/2 x 5 7/8 in.,
Acting
capillary 36 in.
(914 mm) long
LP916A1134
Direct
Bulb 3/8 x 7 in.,
Acting
capillary 36 in.
(914 mm) long
LP916A1175
Direct
Bulb 3/8 x 7 in.,
Acting
capillary 36 in.
(914 mm) long
LP916B1017
Direct
Bulb 1/2 x 5 7/8 in.,
Acting
capillary 36 in.
Heating,
(914 mm) long
Reverse
Acting
Cooling
LP916B1058
Direct
Bulb 1/2 x 5 7/8 in.,
Acting
capillary 36 in.
Heating,
(914 mm) long
Reverse
Acting
Cooling
LP916B1074
Direct
Bulb 3/8 x 7 in.,
Acting
capillary 36 in.
Heating,
(914 mm) long
Reverse
Acting
Cooling
LP916B1082
Direct
Bulb 3/8 x 7 in.,
Acting
capillary 36 in.
Heating,
(914 mm) long
Reverse
Acting
Cooling
LP916B1090
Direct
Bulb 3/8 x 9 in.,
Acting
capillary 36 in.
Heating,
(914 mm) long
Reverse
Acting
Cooling
LP916C1023
Reverse
Bulb 3/8 x 9 in.,
Acting
capillary 36 in.
(914 mm) long
Maximum Operating Pressure: 25 psi (170 kPa)
Accessories:
107324A Capillary Holder Assembly for duct insertion, 8 3/8 in. long
14004376-001 Gasket for 14004378 Connector Assembly
14004378-002 Connector Assembly, with integral 0.005 in. restriction
and filters for post 1984 units
Replacement Parts:
14003113-002 Repair kit containing 0.007 in. restrictor plate, filters, and
gaskets for pre-1984 units
Setpoint
Temperature
Range
Changeover
(F)
(C)
(psi)
(kPa)
65 F to
19 C to
85 F
30 C
65 F to
19 C to
85 F
30 C
40 F to
80 F
65 F to
19 C to
Heat 18 psi,
Heat 124 kPa,
85 F
30 C
Cool 13 psi
Cool 90 kPa
65 F to
19 C to
Heat 18 psi,
Heat 124 kPa,
85 F
30 C
Cool 9 psi
Cool 62 kPa
65 F to
19 C to
Heat 18 psi,
Heat 124 kPa,
85 F
30 C
Cool 13 psi
Cool 90 kPa
65 F to
19 C to
Heat 18 psi,
Heat 124 kPa,
85 F
30 C
Cool 13 psi
Cool 90 kPa
65 F to
19 C to
Heat 18 psi,
Heat 124 kPa,
85 F
30 C
Cool 13 psi
Cool 90 kPa
60 F to
80 F
70-6925
Thermostats
Throttling
Range
(F)
(C)
Includes
3.5 F 2 C
Integral Mounting Bracket
and 304528A Bag
Assembly (mounting
hardware). Order bulb
hangers (316297-00021)
separately.
3.5 F 2 C
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
7 F
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
3.5 F 2 C
Integral Mounting Bracket
and 304528A Bag
Assembly (mounting
hardware). Order bulb
hangers (316297-00021)
separately.
3.5 F 2 C
Integral Mounting Bracket
and 304528A Bag
Assembly (mounting
hardware). Order bulb
hangers (316297-00021)
separately.
3.5 F 2 C
Order Mounting Bracket,
Knob, Bulb Hangers, and
Scale Plate separately.
3.5 F 2 C
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
3.5 F 2 C
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
3.5 F —
Integral Mounting
Bracket, (2) 316297-
00021 Bulb Hangers and
304528A Bag Assembly
(mounting hardware).
Comments
New
installation
model
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents