Rp922 Pneumatic Potentiometer - Honeywell Pneumatic Controls Engineering Manual

Pneumatic controls catalog, cross-reference
Table of Contents

Advertisement

RP922 Pneumatic Potentiometer

Typical Wiring Diagram for RP922
FLOW SIGNAL 2
FLOW SIGNAL 1
3
1
2
Product Number
Operation
RP922A1007
Can sum two input pressures, average two input pressures, be
adjustable flow restriction or be an adjustable pressure supply.
TOTAL CFM
FLOW SIGNAL
C4289
A three-port pneumatic potentiometer can sum two input
pressures, average two input pressures, be an adjustable flow
restriction, or be an adjustable pressure supply. Replacement
devices are available for Johnson, Powers, Robertshaw, Barber-
Colman, and older Honeywell devices.
High efficiency integral filters for all ports.
High reliability, no internal moving parts.
Compact size.
High accuracy.
Type: Pneumatic Averaging / Ratio Relay
Dimensions, Approximate: 2 7/16 in. wide x 1 5/8 in. deep x 2 7/8 in.
high (62 mm wide x 42 mm deep x 73 mm high)
Airflow Usage: Average of two input pressures
Air Connections: Barb fittings 5/32 in. (4 mm) O.D. plastic tubing
Operation: Can sum two input pressures, average two input pressures,
be adjustable flow restriction or be an adjustable pressure supply.
Mounting: Wall or panel or Snap onto DIN rail
Operating Humidity Range (% RH): 5 to 95% RH
Maximum Safe Operating Pressure: 30 psi (205 kPa)
Mounting
Wall or panel or Snap
onto DIN rail
70-6925
Relays
Description
Wall, Snap onto DIN rail or panel mounted
Pneumatic Averaging / Ratio Relay
57