Flex Vent Through The Roof (Vertical) Applications; Vsk7 Vertical Flex Vent Kit Installation - Temco DV1000N/P Installation And Operating Manual

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

8. To finish connections, place a small bead of silicone
to the outside of the fireplace inlet flange. Then, slide
the extension collar over the inlet flange and secure
with the three (3) screws provided.
NOTE: We recommend driving in two (2) sheet metal
screws at 180° adjacent to the gear clamp at each joint.
Flex Vent Through the Roof
(Vertical) Applications
All models are approved for:
1. Vertical venting up to 35' (10.7 m) with 7" x 4" flex.
2. Multiple bends allowed. See section on General
Venting.
3. With each vertical installation, a VSK7MH-2 kit may
be used.
Ceiling Joist
Firestop
Fig. 23 Firestop at ceiling level.
Attic Above Ceiling
(Uninsulated)
Attic Above Ceiling
(Insulated)
Fig. 24 Attic insulation shield.
T190
ceiling install
12/5/03 djt
76657
Room Above
Ceiling Level
T190
Firestop
Attic Insulation
Shield
T190
Temco DV1000/1200/1400 Series
Roof
6' (1.8m)
Maximum
Joists
7" (178 mm) Dia.
Fig. 25 Typical through-the-roof installation.
The VSK7 Kit contains:
• Vertical Termination Cap and Storm Collar
• 4"/7" dia. x 24" Rigid Pipe (unitized)
T191
• 7" dia. Roof Support Components
thru the roof
• 0/12-5/12 Flashing with Storm Collar
installation
• Tube High Temp Sealant
12/5/03 djt
7" dia. Inlet Ext. Collar
• Firestop
• Hardware Pack
• Instruction

VSK7 Vertical Flex Vent Kit Installation

T190
ceiling install
1. Locate the fireplace.
12/5/03 djt
2. Mark ceiling above unit where flex will come through.
*-REFER TO VERTICAL TERMINATION LOCATION
CHART
3. Ceiling opening should be a minimum of 9¹⁄₂" x 9¹⁄₂"
(241 x 241 mm) and framed to that size.
4. Mark opening in roof and cut a hole minimum 9¹⁄₂" x
9¹⁄₂" (241 x 241 mm) and frame to that size.
5. Place fireplace in proper location and secure to the
floor.
6. Install the firestop at the ceiling level.
7. If an attic space (insulated or not) is located above
the ceiling, the firestop should be installed to the
underside of the ceiling. The firestop maintains the
proper air-space clearance from the vent to insula-
Attic Insulation
35' (10.7m)
Shield
Maximum
T191
15