Table 5. Panel Summary Registers (FC 04) (continued)
Name
MIN Frequency
MAX Frequency

Panel Alarms (FC 01 or 02)

Table 6 lists the panel alarms. They are not registers, but are discrete
inputs and are read using FC 01 or FC 02.
To read the Main Breaker Overload alarm at Panel #4, set the Modbus
program to Unit ID 5 and coil address 1254:
IP: <IP address of PDU/RPP>
Unit ID: 5
Starting Register: 1254
Number of Registers: 1
Function Code: 02
Table 6. Panel Alarms (FC 01 or 02)
Name
Neutral Overload
Panel Under Voltage
Panel Over Voltage
Panel Under Over Frequency
Branch Breaker Overload Warning
Branch Breaker Overload
Main Breaker Overload Warning
Main Breaker Overload
EATON Power Xpert
®
Gateway Series 1000 Card User's Guide
MODBUS REGISTERS
Register
Data Type
11022
FLOAT
11027
FLOAT
Coil/Status Address
1219
1238
1242
1248
1249
1250
1253
1254
S
164201670 Rev 1
Bytes
4
4
Data Type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL