Floor Protection; Venting - Breckwell SP 6000 Owner's Manual

Multi-fuel stove
Hide thumbs Also See for SP 6000:
Table of Contents

Advertisement

Floor Protection

Venting

The SP 6000 Multi-Fuel is certified for use with listed TYPE L-Vent, 3" or 4" diameter in size. The stove was tested with
Simpson Duravent brand. Class "A" chimney is not required. Refer to the instructions provided by the vent manufacturer,
especially when passing through a wall, ceiling or roof.
This is a pressurized exhaust system. A
with 500F (260C) RTV silicone sealant and UL-181-AP foil tape to ensure consistent performance and to avoid
SEALED
smoke spillage.
 DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
 DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
 INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
Equivalent Vent Length (EVL)
The longer the length of your exhaust flue, the more restriction there is in the system. Therefore, a larger diameter pipe
should be used. As such, prior to purchasing and installing your unit, you should carefully plan your installation and
calculate the equivalent vent length (EVL) of your planned installation. Use the following to calculate your EVL:
 90º Elbow or Tee
 45º Elbow
 Horizontal Pipe
 Vertical Pipe
If your EVL is less than 15' you may use 3" diameter pipe. However, if your EVL is 15' or greater you must use 4"
diameter pipe. If your exhaust configuration has three elbows, or if you have a corner installation going out a sidewall,
4" diameter pipe should be used regardless of your EVL calculation.
NOTE: F
OR BEST PERFORMANCE LIMIT THE AMOUNT OF HORIZONTAL PIPE AS MUCH AS POSSIBLE
.
OF HORIZONTAL PIPE
NOTE: A
T ALTITUDES ABOVE
INSTALLATION
LL VENT CONNECTOR JOINTS MUST BE SECURED WITH AT LEAST THREE SCREWS AND
= 5 Feet
= 3 Feet
= 1 Foot per actual foot (actual measurement)
= ½ Foot per actual foot (1/2 of actual measurement)
3,000
, 4"
FEET
PIPE IS REQUIRED WITH AN
Freestanding installations require a minimum 33 ¼" wide by 36"
long floor protection. The stove must be placed on a continuous
(grouted joints) noncombustible material such as ceramic tile,
cement board, brick, 3/8" millboard or equivalent, or other
approved or listed material suited for floor protection.
THE MATERIAL(S) USED MUST HAVE, OR COMBINE TO
HAVE, A MINIMUM INSULATIVE RATING OF 'R1'.
NOTE: C
,
ERAMIC TILE
OR ANY OTHER TILE
CONTINUOUS SHEET OF NON
PREVENT THE POSSIBILITY OF EMBERS FALLING THROUGH TO THE
COMBUSTIBLE FLOOR IF CRACKS OR SEPARATION SHOULD OCCUR IN
. T
THE FINISHED SURFACE
-
BUILT
IN RAISED HEARTHS
.
ALTERNATIVES
Clearances are measured from the sides, back and face (door
opening) or stove body.
DO NOT USE MAKESHIFT MATERIALS OR COMPROMISES
IN THE INSTALLATION OF THIS UNIT.
EVL
7'
OF
OR MORE
2
,
REQUIRES A
-
COMBUSTIBLE MATERIAL BENEATH TO
HIS INCLUDES FLOOR PROTECTION FOR
. C
HECK LOCAL CODES FOR APPROVED
. Y
OU SHOULD NEVER HAVE MORE THAN
.
5'

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents