230/240V PDU Rack Power Configurations

Configurations for the 230/240 VAC, PDU options are shown in the text below,
Table
, and Figure
3-2
230/240 VAC Power Configuration
In a country with a 230/240 VAC power system, the wide range (200/240 V) PDU
model E7671A is required. If you are using a UPS, attach the C-19 end of the
accompanying power cord to the PDU and attach the C20 end of the same cord to
the IEC 320 receptacle in the rear of the UPS.
Alternate 230/240 VAC Power Configuration
When the 230/240 VAC PDU is to be used without a UPS in the rack, the PDU is
shipped with a localized power cord.
NOTE
Only localized power cords rated 16A will allow the full 16A
rating of the PDU to be used.
For use with 230/240 VAC power mains, direct connection to a junction box is
usually necessary. In this case, an unterminated power cord is supplied. Be sure to
obey all local electrical code requirements when connecting to the site electrical
power supply.
Procedure for Connecting and Routing Cables to the LXr 8500
.