Chapter 2
Table 2-2. LXr 8500 Plugs and Receptacles Reference
LXr 8500 Jumper Cord
RackStorage/12 and /12FC
and PDU Jumper Cord
PDU Model No.
Can PDUs be "Daisy
Chained"?
PDU Linecord style
PDU linecord for
recommended UPS
Alternate PDU linecords
for installations without a
UPS
UPS APC Model Number
APC Redundant Switch
between PDU and Branch
Circuits (No UPS)
Redundant Switch between
UPS and Branch Circuit
Note 1. Limit the 10-amp PDU to 10 amps of capacity, plug it into the 16-amp PDU, and
limit both together to 16 amps of capacity.
Note 2. The CEE 7/7 cord is fused for 13-amp loads, and limits the PDU to 13 amps of total
supply.
Note 3. The circuit load should be limited to 3000 VA when this switch is used.
Note 4. The circuit load should be limited to 3000 VA when this switch is used.
208 VAC Mains
included
C19 to C20, 2.5 m
E7742A, 90 inch (2.5 m), C13
to C14
E7671A (16 Amp)
E7672A (16 amp, cord, and
10 amp)
Yes, 10 amp plugs into 16
amp (use to extend the
1
number of receptacles)
Detachable
E7803A, 4.5m, with NEMA
L6-20P plug to C19
E7803A, 4.5m, NEMA L6-
20P to C19 plug
E7805A 4.5 m with NEMA
L6-30P to C19
NS3000RMT3U
SU045-1 with captive L6-20P
line cords and E7803A, 4.5 m,
3
L6-20P to C19 to PDU
SU045-1 with captive line
cords, captive UPS L6-20 P
3
connects to L6-20R in switch
Rack Cabling References
230/240V Mains
included
C19 to C20, 2.5 m
E7742A, 90 inch (2.5 m),
C13 to C14
E7671A (16 Amp)
E7672A (16 amp, cord, and
10 amp)
Yes, 10 amp plugs into 16
amp (use to extend the
1
number of receptacles)
Detachable
E7804A, 4.0m, with IEC
C20 to C19 plug,
E7806A, 4.5 m, C19 to
unterminated
E7804A, 4.5 m, C20 to C19
E7809A, 4.5 m, CEE 7/7 -
2
C19
NS2200RMI3U or
NS3000RMI3U
SU044-1, C20 inputs,
country-specific C19 cords,
and E7804A, 4 m, C20 to
4
C19 jumper cord to PDU
SU044-1, C20 inputs,
country-specific C19 cords,
and E7804A, 4 m C20 to
4
C19 jumper cord to UPS