When (in either the 208 or 230/240 VAC case) a 10-amp PDU is daisy-chained to
a 16-amp PDU, determine the load to be placed on each. Plug only those
combinations of components into the 10-amp PDU whose overall total current
draw is less than 10 amperes. Then be sure that the 16-amp PDU total load,
including the daisy-chained 10-amp PDU and any other components, does not
exceed 16 amperes.
Add more PDU-UPS circuits to support higher loads.
Figure 3-2. Power Connection Locations on a Typical Rack (Rear View)
36
Procedure for Connecting and Routing Cables to the LC 2000r