Chapter 2
Table 2-8. 200/208 VAC Power and Current:
Approximate Requirements of Rack Optimized Devices and Components
Device
(Notes 1, 2, 3)
HP NetServer LC 2000r
HP NetServer LH 3000r
HP NetServer LH 6000r
HP NetServer LT 6000r
HP NetServer LPr
HP NetServer LXr 8000 and
LXr 8500 (Note 4)
HP NetServer LH 4r
HP NetServer LH 3r
HP NetServer LXr Pro8
HP NetServer LXr Pro
HP Fibre Channel Hub D6976A
HP Rack Storage/12FC
HP Rack Storage/12
Monitor (14-inch)
Monitor (15-21-inch)
DLT Library
DLT Mechanism
HP SureStore Autoloader 418
DAT 24x6e
DAT 24e
Console Switch
Note 1 Indicated current ratings are approximate, for use in selecting PDU and UPS
components, and may not reflect actual measured amounts.
Note 2 For a full list of power ratings, see the rack configuration utilities (for instance,
Rack Assistant) on the HP Web Site.
Note 3 Ratings from previously published estimates are updated.
Note 4 Ratings assume upgrade from HP NetServer LXr 8000 to HP NetServer LXr 8500
with no change to rack power subsystem.
Rack Cabling References
Input Power
Input Power
(VA)
(W)
516
506
792
777
1120
1099
792
777
640
285
1121
1077
1130
1100
650
626
980
970
450
446
140
125
522
512
522
512
125
88
200
140
140
98
50
35
214
150
16
11.2
6
4.2
42
29
208v IRMS
(Amps)
2.5
3.7
5.3
3.7
3.2
5.6
5.7
3.2
4.9
2.3
0.7
2.6
2.6
0.6
0.7
0.7
0.3
1.1
0.1
0.1
0.2
27