Elan V883 Installation Manual page 26

Elan home systems video controller installation manual v883 v series
Hide thumbs Also See for V883:
Table of Contents

Advertisement

V883
INSTALLATION MANUAL
RS-232 Control
SYMPTOM
No source or zone selected
from RS-232 controller.
Incorrect source and/or zone
selected.
Acknowledgement
&V883,ACK,xxx<CR> is not
received within 200ms
VIA!NET Control
SYMPTOM
No source or zone selected
from VIA!NET controller (VIA!
Touch Panel, etc.).
Incorrect source and/or zone
selected.
Page 24
CAUSE
1. RS-232 controller incorrectly
programmed.
2. RS-232 signal path wiring bad.
3. UNIT ID DIP switches incorrect.
4. BAUD RATE switches incorrect. Verify/correct DIP switches.
The V883 RS-232 commands
were incorrectly programmed.
1. The command was formatted
incorrectly.
2. An error has occurred in the
V883.
3. Serial cable not connected
or defective.
4. V883 does not have power.
CAUSE
1. VIA!NET controller not
programmed.
2. VIA!NET signal path wiring bad.
3. UNIT ID DIP switches incorrect.
Incorrect V883 VIA!NET com-
mands programmed.
E L A N H O M E S Y S T E M S
SOLUTION
Verify/correct programming.
Verify RS-232 wiring. Check wire
integrity an pin-out configuration.
Verify/correct DIP switches.
Verify/correct programming.
Verify/correct programming.
Turn unit OFF, then back ON.
Connect or replace serial cable.
Connect power, check breakers.
SOLUTION
Program VIA!NET controller.
Verify VIA!NET wiring.
Verify/correct DIP switches.
Verify/correct programming.
© ELAN Home Systems 2006 • All rights reserved.
©