4. Operation
4.8

Configuring Battery Settings

Set the UPS for the number of EBMs installed whether to run automatic battery tests, and automatic
restart configuration.

Configuring the UPS for EBMs

To ensure maximum battery runtime, configure the UPS for the correct number of EBMs:
1. Press any button on the front panel display to activate the menu options, then select SETTINGS,
USER SETTINGS, and NUMBER OF BATTERY STRINGS.
2. Use the
Table 6. EBM vs number of Battery strings
All UPS and EBM Cabinets
UPS only (internal batteries)
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
UPS + 4 EBMs
NOTE: if 0 is selected, no batteries are connected and all battery-related alarms are disabled.
NOTE: the UPS contains one battery string; each EBM contains two battery strings.
3. Press the
4. Press the
Running Automatic Battery Tests
Automatic battery tests run approximately every 30 days, unless disabled. During the test, the UPS
transfers to Battery mode and discharges the batteries for 25 seconds under the existing load.
The "UPS on Battery" notice and the "Battery Low" alarm do not activate during a battery test.
For automatic battery tests to run:
the "Automatic Battery Support Tests" setting must be enabled.
the UPS must be in Normal mode, with no active alarms.
the batteries must be fully charged.
the bypass voltage must be acceptable.
no manual battery test was initiated previously in the same charging cycle.
To pass the battery test, the battery voltage must remain above the threshold value during discharge.
Configuring Automatic Restart
The UPS automatically restarts if utility returns after the output was shut off due to exhausted batteries,
a shutdown input signal, or automatic shutdown command.
You can set the load segment for the amount of time to delay the restart once utility returns, using the
"Automatic Start Delay" setting. You can also configure UPS restart to depend on the battery charge
level, using the "Battery Charge % to Restart" setting.
Page 20
or
buttons to select the number of battery strings according to your UPS configuration:
Number of Battery Strings
1 (default)
3
5
7
9
button to save the setting.
button until the start screen appears.
ESC
9130 UPS-EN