Eaton 9130 Series Firmware Upgrade Instructions

Eaton 9130 Series Firmware Upgrade Instructions

Dsp

Advertisement

Quick Links

Eaton 9130 Series
DSP firmware upgrade instructions
10 28 349 Revision P4
2012-04-27

Advertisement

loading

Summary of Contents for Eaton 9130 Series

  • Page 1 Eaton 9130 Series DSP firmware upgrade instructions 10 28 349 Revision P4 2012-04-27...
  • Page 2 9130 firmware upgrade guide 1028349 Rev. P4 Introduction This document gives a guidance of how to upgrade (flash) the Main (DSP) of Powerware 9130 series UPS. Available firmware updates and required software tools can be downloaded from http://www.powerware.com/software/downloads.asp. Purpose Periodically, Eaton releases firmware upgrades for some of its products.
  • Page 3: Quick Reference

    7. Press “Open File”, and select an “S” file to be flashed (e.g. V1.22.S). 8. Press “Flash Normal” and unplug input power cord from the UPS. 9. Wait until “Flash ok” notice will appear and press “Close” button.  2012, Eaton Corporation Page 3 of 11...
  • Page 4  Settings Serial Port Configuration Port: RS232, Speed: 9600. 3. Connect the RS-232 cable between DB-9 connectors of the computer and the UPS. 4. Start Watcher - UpsFlash software from the computer.  2012, Eaton Corporation Page 4 of 11...
  • Page 5 5. Choose the right COM port (typically COM1) and Bit rate “9600”, then press to open COM port. Choose “Ups Flash” Tab. 6. Press and select “S” file to be flashed and click  2012, Eaton Corporation Page 5 of 11...
  • Page 6 . The flashing will begin after a few seconds. Note. If “Flash firmware NG!” message will appear during the flashing, go to Chapter 1.3 DSP Firmware Upgrading via RS-232 – Flash Error.  2012, Eaton Corporation Page 6 of 11...
  • Page 7 9130 firmware upgrade guide 1028349 Rev. P4 9. The LCD display “Flashing in progress…”. Wait until the “Flash OK” message will appear. Click buttons and exit from the software.  2012, Eaton Corporation Page 7 of 11...
  • Page 8 COM port. 3. Press button and select “S” file to be flashed (e.g. V1.22.S) and click 4. Click button. The DSP flashing should begin after a few seconds.  2012, Eaton Corporation Page 8 of 11...
  • Page 9 9130 firmware upgrade guide 1028349 Rev. P4 5. Wait until the “Flash OK” message will appear. Click buttons and exit from the software.  2012, Eaton Corporation Page 9 of 11...
  • Page 10 9130 firmware upgrade guide 1028349 Rev. P4  2012, Eaton Corporation Page 10 of 11...
  • Page 11 2. Restart LanSafe Power Monitor service if it was stopped by running Services.msc from Windows command prompt and there click on LanSafe Power Monitor and select “Start the service”.  2012, Eaton Corporation Page 11 of 11...