7. Specifications
Table 18. Electrical Input
Model
PW9130i5000T-XL
PW9130i6000T-XL
208 V are derated by 10 %.
Table 19. Electrical Input Connections
Model
PW9130i5000T-XL
PW9130i6000T-XL
Table 20. Electrical Output
All Models
Voltage Regulation
Efficiency
Frequency Regulation
Nominal Outputs
Frequency
Output Overload
Output Overload
(Bypass Mode)
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Factor
Table 21. Electrical Output Connections
Model
PW9130i5000T-XL
PW9130i6000T-XL
Page 32
Default Input
(Voltage/Current)
230 V / 21.7 A
230 V / 26.1 A
Input Connection
Hardwired
Normal Mode
±2 %
> 98 % (High Efficiency mode),
> 94 %
Sync with line ±3 Hz of nominal line
frequency (outside this range: ±0.1 Hz
of auto-selected nominal frequency)
High Voltage Models
200/208/220/230/240V (voltage configurable or auto-sensing)
5000/6000 VA 4.5/5.4 kW
50 or 60 Hz, autosensing or configurable as a frequency converter
100–102 %: Activates Overload alarm (Level 1)
102–129 %: Load transfers to Bypass mode after 2 minutes (Level 2)
130–149 %: Load transfers to Bypass mode after 30 seconds (Level 3)
≥ 150 %: Load transfers to Bypass mode after 100 ms (Level 4)
100–109 %: Activates Overload alarm (Level 1)
110–129 %: UPS shuts down after 5 minutes (Level 2)
130–149 %: UPS shuts down after 30 seconds (Level 3)
≥ 150 %: UPS shuts down after 300 ms (Level 4)
Sine wave
< 3 % THD on linear load;
< 5 % THD on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10 ms maximum (due to loss of utility)
0.9
3 to 1
Output Connections
Hardwired
Selectable Input
Voltage Range
200*, 208*, 220, 230, 240
200*, 208*, 220, 230, 240
Input Cable
None
Battery Mode
Nominal output voltage ±3 %
> 92 %
±0.1 Hz of auto-selected nominal
frequency
Output Cables
None
Voltages
at 100 % Load
180–276 Vac
180–276 Vac
9130 UPS-EN