Communication; Installing Communication Options And Control Terminals; Communication Options - Eaton 9130 User Manual

5000 - 6000 va
Hide thumbs Also See for 9130:
Table of Contents

Advertisement

This section describes the:
Communication ports (RS-232 and USB)
Connectivity cards
Remote Power-off (RPO)
Relay output contacts
Programmable signal inputs
Modem operation
EATON® Power Management Software
Relay output
RPO
USB
RS232
Interface Com
External battery
(EBM)
Figure 21. Communication Options and Control Terminals.
5.1

Installing Communication Options and Control Terminals

To install the communication options and control terminals:
1. Install the appropriate connectivity card and/or necessary cable(s) and connect the cables to the
appropriate location.
See Figure 21 and the following section, "Communication Options", for detailed information.
2. Route and tie the cable(s) out of the way.
3. Continue to "Operation" on page 14 to start up the UPS.
5.2

Communication Options

The Eaton 9130 has serial communication capabilities through the USB and RS-232 communication
ports or through a connectivity card in the available communication bay.
The UPS supports two serial communication devices according to the following table 7:
Independent
Communication Bay
Any connectivity card
Any connectivity card
You can configure relays, signal inputs, and the serial port baud rate through the front panel
menus (see table 4 on page 15).
The communication speed of the USB port is fixed at 9600 bps.
9130 UPS-EN
Multiplexed
USB
Available
Not in use

5. Communication

RS-232
Not in use
Available
Page 21