Replacing The Scsi I/O Module; Before You Begin; Verifying Component Failure; Removing The Component - HP 201723-B21 - StorageWorks Modular SAN Array 1000 Hard Drive Maintenance And Service Manual

Modular smart array
Hide thumbs Also See for 201723-B21 - HP StorageWorks Modular SAN Array 1000 Hard Drive:
Table of Contents

Advertisement

Replacing the SCSI I/O module

CAUTION:
The SCSI I/O module with an integrated EMU is not hot-pluggable. Before replacing the module, all I/O
from the servers must be stopped and the MSA must be powered down.

Before you begin

CAUTION:
Before removing a component or blanking panel from an operational device, make sure that you
have the replacement part available. Removing a component or blank impacts the airflow and
cooling ability of the device. To avoid possible overheating, insert the new or replacement component
within one or two minutes. If the internal temperature exceeds acceptable limits, the device may
overheat and automatically shut down or restart.
Parts can be damaged by electrostatic discharge. Use proper anti-static protection.

Verifying component failure

Before replacing the SCSI I/O module:
Verify that the module status LED is not illuminated or is flashing amber.
Check the array controller LCD display panel for error messages and take appropriate action.

Removing the component

1.
Review all warnings, cautions, and preparation procedures as detailed in
NOTE:
Before removing the SCSI I/O module, label all cables. This ensures their reconnection in
the correct configuration.
2.
Disconnect all SCSI cables from the SCSI I/O module.
3.
Press down on the SCSI I/O module latch (1) and pull the SCSI I/O module out of the enclosure (2).
90
Customer replaceable components
Warnings and
1
2
1 5 559
precautions.