Mini C Series VRF 50/60Hz
2.16 P1: Discharge pipe high pressure protection (for 100~160 model)
2.16.1 Digital display output
P1
2.16.2 Description
Discharge pipe high pressure protection.
The system stops running.
Error code displayed on the outdoor unit PCB.
2.16.3 Trigger / recover condition
Trigger condition: Discharge pressure ≥ 4.4MPa.
Recover condition: Discharge pressure ≤ 3.2MPa.
Reset method: Resume automatically.
2.16.4 Possible causes
Pressure sensor/switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.