Mini C Series VRF 50/60Hz
2.14 H0: Communicate malfunction between inverter module board and main control board (for all models)
2.14.1 Digital display output
H0
2.14.2 Description
Communicate malfunction between inverter module board and main control board protection.
The system stops running.
Error code displayed on the unit with the error.
2.14.3 Trigger / recover condition
Trigger condition: Communicate malfunction between inverter module board and main control board.
Recover condition: Communicate between inverter module board and main control board is normal.
Reset method: Resume automatically.
2.14.4 Possible causes
DC fan motor damaged.
Main control board damaged.
Filter board damaged (100/120 model can ignore this reason for they don't have a filter board).
2.14.5 Procedure
Power off for 3 minutes, and disconnect
the DC fan motor connection port,
repower on to confirm whether the fault
is cleared
Main control board damaged.
64
H0
No
Yes
DC fan motor malfunction
Need help?
Do you have a question about the Mini C Series and is the answer not in the manual?