2.13 F1: DC bus voltage protection (Only for 100~160 model)
2.13.1 Digital display output
F1
2.13.2 Description
 F1 indicates DC bus voltage protection.
 The system stops running.
 Error code displayed on the outdoor unit PCB.
2.13.3 Trigger / recover condition
Trigger condition: If IC55 main chip couldn't receive the DC generatrix voltage detection signal or the voltage less than 200VDC in the first
5 seconds period when power on, it would report F1 and the big relay is forbid to close.
Recover condition: IC55 main chip can receive the DC generatrix voltage detection signal and the voltage over 200VDC .
Reset method: Resume automatically.
2.13.4 Possible causes
DC fan motor damaged.
Main control board damaged.
Filter board damaged (100/120 model can ignore this reason for they don't have a filter board).
2.13.5 Procedure
Check LED301 Is
Check the wiring between main control
board and filter board is correct or not.
Voltage of power supply is 166-265V?
F1
flashing or not
Yes
Yes
Mini C Series VRF 50/60Hz
No
Replace outdoor main PCB
No
Connect again
Provide normal power supply
No
63