CF displays if the jack is not connected, or the bot-
tle is full, or the bypass plug is not inserted proper-
ly.
D. CONNECT THE EXTERNAL CONDENSATE TANK TO SYSTEM
1. Remove the factory-installed condensate float switch-bypass plug located in the power
cord pocket at the back of the KPHP.
2. Install the male connector jack (supplied) onto the condensate tank.
3. Connect the factory supplied ¼-inch ID condensate tubing to the ¼-inch OD barbed con-
densate water outlet on the back of the KPHP.
4. Connect the discharge end of the tube to the ¼-inch barbed connector on the condensate
tank.
5. The condensate float jack must be inserted into the female condensate plug to operate
the KPHP. CF displays if the jack is not connected, or the bottle is full, or the bypass plug
is not inserted properly.
6. Empty the bottle when full by removing the jack and drain line and empty the bottle in an
approved location.
E. CONNECT CONDENSATE PUMP TO A DRAIN LOCATION
1. Connect ¼-inch ID tubing to the ¼-inch OD barbed fitting located in the power cord pock-
et on the back of the KPHP.
2. Pump condensate water up to 20 feet straight up and out over 100 feet to an approved
drain source, or use the external condensate tank that comes standard with the system.
The 5-gallon condensate tank is equipped with a
float switch that shuts the unit's compressor off and
alerts operators with an alarm and displays CF
("Condensate Full") when the condensate tank is
full. This prevents accidental water overflow on the
floor.
3. The alarm clears automatically upon the operator emptying the 5-gallon tank and recon-
necting it. If connecting to a permanent drain, do NOT connect or use the equipped tank.
Refer to Section VII, Maintenance.
F. CEILING KIT (OPTIONAL ACCESSORY)
The ceiling kit is comprised of flanges with foam tape, fasteners, two (2) eight-foot lengths of
flexible duct, duct clamps, and one 24-inch X 24-inch replacement ceiling tile for KPHP 1811
and two 24-inch X 24-inch replacement ceiling tiles for KPHP 2211.
1. Align the holes of the flange to the holes located on the top of the unit. Attach to the top of
the KwiKool System using the factory supplied fasteners.
2. Attach each duct to the flanges on the replacement ceiling panel(s); secure the duct to
each flange using the supplied clamps.
NOTE