SECTION II - INSTALLATION AND ASSEMBLY
The KPHP system provides a portable heat pump to match customer needs. These systems
come with touchscreen controls, condensate pumps and other features. These heat pumps
replace the need for heat strips. Models1811 provides heat in a 1.5-ton option and cooling in
the 1.1-ton option. Model 2211 provides a 1.8-ton heating option and a 1.5 ton cooling option.
A. PREVIEW THE INSTALLATION SITE
Before moving the KwiKool System into place, verify the following:
The direction to which the Supply Air is going.
The direction from which the Return Air is coming (cooling).
The direction to which the Hot Air exhaust is going (heat removal).
The direction from which the Condenser Make-up Air is coming.
The location of the power supply.
The area to which the condensate water will be pumped or collected.
Position the unit based on these guidelines for best results.
B. AIR CHUTES (IF EQUIPPED OR AS AN OPTIONAL ACCESSORY)
Install Supply Air flanges with the supplied fasteners to the front of the KwiKool System
above the control panel. Use the supplied clamps to attach the air chutes to the collars. See
instructions in the air chute kit for specific instructions.
C. CONDENSATE TANK
KwiKool Systems come standard with an external 5-gallon condensate tank. The external
condensate tank is equipped with a float switch that shuts the KPHP down and alerts opera-
tors with an alarm and displays CF ("Condensate Full") when the condensate tank is full. This
prevents accidental water overflow on the floor.
NOTE
Leave at least five feet of open space around the
Return Air inlets to ensure proper operation.
CAUTION
The alarm will clear automatically upon emptying
the 5-gallon tank and reconnecting it. If connecting
to a permanent drain, do NOT connect or use the
equipped tank.
PRUDENCE
L'alarme s'effacera automatiquement une fois le ré-
servoir de 5 gallons vidé et reconnecté. Si vous
vous connectez à un drain permanent, ne connect-
ez PAS et n'utilisez PAS le réservoir équipé.