Installation clearances (Fig. 41)
The minimum installation clearance measurements of the Ø
80/80 separator terminal kit have been stated in some limit condi-
tions.
* Configuration C
envisages connection to flues working with nat-
4
ural draught.
For technical data concerning the C
please refer to the table in par. 4.2.
Extensions for separator kit Ø 80/80 (L = Equivalent length - L max = Maximum length).
To aid in the removal of possible condensate forming in the exhaust pipe, tilt the pipes towards the appliance with a minimum
slope of 5% (Fig. 42).
Please note the type of installation C
Key (Fig. 42):
A
-
Intake
X
-
Minimum slope 5%
S
-
Exhaust
L
-
Equivalent length
The maximum lengths ((L max) of the various flues that can be installed are given in the summary table in parag. 1.22.
configuration,
4
must be done with a natural draught flue.
43
S
3 m
X
L0
L = TA + L1 + C2 + C1 + L0
L ≤ L max
ST.008706/000
TA
C1
C2
A
L1
L max -
Maximum length
TA
-
Intake terminal Ø80/80
C1
-
Ø80/80 90° elbow
C2
-
Ø80/80 90° elbow
Magis Combo 12/14/16 Plus V2 I
C
*
43
41
C
83
80 mm
42
51