3.13 CO
ADJUSTMENT
2
Calibration of minimum CO
Enter the chimney sweep phase without withdrawing domestic hot water and take the selector switches to minimum until "0" is seen on
the display.
To have an exact value of CO
specified in the table, otherwise adjust the screw (Det. 3, Fig. 80) (Offset regulator).
To increase the CO
value, turn the adjustment screw (3) in a clockwise direction and vice versa to decrease it.
2
Calibration of maximum CO
On completion of the adjustment of the minimum CO
maximum (increase the value until "99" is seen on the display).
To have an exact value of CO
specified in the table below, otherwise adjust the screw (Det. 12, Fig. 80) (gas flow rate regulator).
To increase the CO
value, turn the adjustment screw (12) in a clockwise direction and vice versa to decrease it.
2
At every adjustment variation on the screw 12 it is necessary to wait for the heat generator to stabilise itself at the value set (about 30 sec.).
Gas type
G20
G31
In the case of an annual inspection of the device, the max CO must be less than 700 ppm (0% O
device requires maintenance/repair.
3.14 FIRST IGNITION PARAMETER SETTING
During the first activation of the appliance, it is necessary to customise the following parameters, which concern the generator opera-
tion, the type of Outdoor Unit and the type of system connected to the appliance.
Heat pump power
Set parameter A11 according to the type of Outdoor Unit connected.
Circulator speed
It is necessary to adjust the pump speed according to the appliance power, to improve the operating efficiency of the machine.
It is suggested to check the values as indicated in the following table:
Number of zones
Set parameter A13 according to the number of zones in the system that are directly controlled by the machine.
(minimum central heating output).
2
the technician must insert the sampling probe in the sample point, then check that the CO
2
(nominal central heating output).
2
keeping the chimney sweep function active, take the heating selector switch to
2
the technician must insert the sampling probe in the sample point, then check that the CO
2
CO
to Nominal Q.
2
9,4 (9,2 ÷ 9,6) %
10,3 (10,1 ÷ 10,5) %
Output
12
14
16
ST.008706/000
CO
Parameter A04
80%
87%
100%
Magis Combo 12/14/16 Plus V2 I
value is that
2
value is that
2
to Minimum Q.
2
8,6 (8,4 ÷ 8,8) %
9,6 (9,4 ÷ 9,8) %
). If the CO value is higher, the
2
125