Measurement of parameters of RCD
Nominal working voltage U
Working range of voltage: 95...270 V
Nominal network frequency f
Working range of frequency: 45...65 Hz
RCD trigger and trip time test t
Test range according to IEC 61557: 0 ms ... to the upper limit of displayed value
Type of RCD
Standard and
short-time delay
Selective
1)
for I
= 10 mA and 0,5 I
n
Accuracy of residual current setting:
for 1*I
, 2*I
and 5*I
n
n
.................................................................................... –8..0%
for 0,5*I
n
Effective value of sink current at measurement of RCD trip time
I
n
10
30
100
300
500
1000
I
n
10
30
100
300
500
1000
* - does not apply to U
56
: 110 V, 115 V, 127 V, 220 V, 230 V, 240 V
n
: 50 Hz, 60 Hz
n
(for t
mode).
A
A
Multiplication
Test range
factor setting
0.5 I
n
1 I
n
2 I
n
5 I
n
0.5 I
n
1 I
n
2 I
n
5 I
n
accuracy is ± 2% m.v. ±3 digits
n
..................................................................... 0..8%
n
Multiplication factor setting
0.5
5
3.5
15
10.5
10.5
50
35
150
105
105
250
175
175
500
Multiplication factor setting
2
20
40
60
84
200
280
280
600
840
840
1000
= 110 V, 115 V and 127 V
n
MPI-525 – USER MANUAL
Resolution
0..300 ms
0..150 ms
0..40 ms
0..500 ms
0..200 ms
0..150 ms
3.5
5
10
15
30
35
50
100
150
300
500
1000
40
40
50
84
120
150
400
500
Accuracy
± 2% m.v. ±2 digits
1 ms
1
20
20
42
42
140
140
420
420
700
700
5
100
100
210
210
700
700
1)
20
60
200
600
1000*
100
300
1000*