Sequence of Operation
Table 33.
Outdoor air damper minimum ventilation control
Traq
Enabled/Active
Enabled/Active
Disabled
Disabled
Disabled
Disabled
During normal occupied periods of heating and cooling
modes of operation, the outdoor air damper maintains
ventilation requirements via the minimum position control
methods. However, the following modes of operation will
override the damper minimum position setpoint to 0%.
•
Morning Warm Up
•
Pre cool
•
Night Purge
•
Unoccupied Heat
78
Outdoor Air Flow
Demand Control
Compensation
Ventilation
Disabled
Disabled
Disabled
Enabled/Active
Enabled/Active
Disabled
Enabled/Active
Enabled/Active
Disabled
Enabled/Active
Disabled
Disabled
Description
Damper controls to outdoor
air minimum flow setpoint
Outdoor Air Flow setpoint is
reset based on space CO
Outdoor Air Damper
Minimum Position is reset
based on supply fan speed.
Outdoor Air Damper
Minimum Position is reset
based on supply fan speed
and space CO2.
Outdoor Air Damper
Minimum Position is reset
based on space CO
.
2
Outdoor air damper position
is controlled by cooling
•
Unoccupied Cool
•
Off
Relief Fan and Space Static
Pressure Control
The primary role of relief fan is to relieve air from the
building to control space static pressure. This is common
Outdoor Air Damper
Controlling Setpoints
Setpoint:
Outdoor Air Minimum Flow
Setpoint Active
Outdoor Air Minimum Flow
Setpoint Status
Setpoint:
.
Outdoor Air Minimum Flow
2
Setpoint Status
Settings:
Design Min Outdoor Air Flow
Setpoint
DCV Min Outdoor Air Flow
Setpoint
Setpoint:
Economizer Minimum
Position Setpoint Active
Settings:
Design Min OA Damper Pos
Setpoint Max Fan
Design Min OA Damper Pos
Setpoint Mid Fan
Design Min OA Damper Pos
Setpoint Min Fan
Setpoint:
Economizer Minimum
Position Setpoint Active
Settings:
Design Min OA Damper Pos
Setpoint Max Fan
Design Min OA Damper Pos
Setpoint Mid Fan
Design Min OA Damper Pos
Setpoint Min Fan
DCV Min Outdoor Air Dampr
Pos at Max Fan
DCV Min Outdoor Air Dampr
Pos at Min Fan
Setpoint:
Economizer Minimum
Position Setpoint Active
Settings:
Design Min OA Damper
Position
DCV Min Outdoor Air
Damper Pos Setpoint
Setpoint:
Economizer Minimum
Position Setpoint Active
RT-SVX080A-EN