Download Print this page

Trane IntelliPak 3 with Symbio 800 Installation, Operation And Maintenance Manual page 57

Commercial rooftop air conditioners

Advertisement

Table 19. Outside air damper travel adjustment
Outside Air Damper
Crank Arm Hole
Configuration
Position
1
1 - 3
2
1 - 4
3
1 - 6
4
2 - 5
5
2 - 7
6
2 - 8
Table 20. Outside air damper pressure drop — No Traq™
CFM
#1
4000
0.06
6000
0.11
7000
0.14
8000
0.18
9000
0.22
10000
0.27
11000
0.32
12000
0.37
13000
0.43
8000
0.17
10000
0.25
12000
0.36
14000
0.48
16000
0.62
18000
0.78
20000
0.95
22000
1.14
24000
1.34
RT-SVX080A-EN
Return Air Damper Crank
Arm Hole Configuration
90°
9 - 11
90°
75°
9 - 12
75°
60°
9 - 13
65°
40°
10 - 14
40°
31°
20°
No Traq™
Outside Air Damper Position
#2
#3
20, 25 and 30 Ton
0.07
0.08
0.14
0.17
0.21
0.25
0.28
0.35
0.36
0.46
0.45
0.58
0.56
0.72
0.67
0.88
0.80
1.05
40, 50 and 55 Ton
0.34
0.40
0.47
0.56
0.60
0.73
0.75
0.93
0.92
1.15
1.09
1.38
1.28
1.64
1.49
1.92
1.71
2.22
#4
#5
0.16
0.24
0.36
0.60
0.49
0.83
0.65
1.11
0.83
1.42
1.02
1.78
1.24
2.17
1.48
2.60
1.74
-
0.84
1.69
1.24
2.48
1.72
-
2.28
-
2.91
-
-
-
-
-
-
-
-
-
Installation
#6
0.87
2.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
57