Download Print this page

Trane IntelliPak 3 with Symbio 800 Installation, Operation And Maintenance Manual page 32

Commercial rooftop air conditioners

Advertisement

A2L Information
Provide an output to energize additional mechanical
ventilation (if needed).
Units without airflow proving will disable electric heat
sources.
Building fire and smoke systems may override this function.
If the refrigerant sensor has a fault, is at the end of its life,
or is disconnected, the unit will initiate the mitigation
32
actions. Mitigation actions may be verified by disconnecting
the sensor.
The refrigerant sensors do not need service. Use only
manufacturer-approved sensors when replacement is
required.
RT-SVX080A-EN

Advertisement

loading
Need help?

Need help?

Do you have a question about the IntelliPak 3 with Symbio 800 and is the answer not in the manual?

Questions and answers