10
INPUT SETUP & CALIBRATION
5
INPUT SETUP & CALIBRATION
5.1
Enter calibration PIN
YOU WILL HAVE THE OPPORTUNITY TO CHANGE YOUR PIN NUMBER AT THE END OF THIS
SECTION (5.8). IF YOU HAVE FORGOTTEN YOUR PIN NUMBER, SEE SECTION 8.
A
Enter the calibration mode by pressing the
_ _ _ ENTER CAL PIN NUMBER scrolls across the display and toggles with 0.
Use the
press
. If the correct PIN is entered, setup is started at 5.2.
P
If an incorrect PIN number is entered, _ _ _ INCORRECT PIN NUMBER – ACCESS
DENIED scrolls across the display and it returns to normal operating mode.
5.2
Input setup
INPUT DEFAULTS ARE SET TO 4-20MA, 50HZ, NO DECIMAL AND NO ROUNDING.
A
_ _ _ INPUT SETUP
skip to 5.3, or the
B
_ _ _ MAINS FREQUENCY
selection. Use the
to accept.
P
C
_ _ _ INPUT MODE
selected input mode. Using the
(0-20mA), 2V (0-2V) or 10V (0-10V). Then press
If you opt to change the input mode in this section then the header plug on the input module may
also need to be changed. See 3.2 for more information.
TEX-BAR-MAN-11V04 (SEP11)
and
buttons to enter your security code (factory default 1). Then
scrolls across the display and toggles with SKIP. Press
button and then
scrolls across the display and toggles with the current
and
buttons to select 50HZ or 60HZ, and then press
scrolls across the display and toggles with the currently
button.
P
to ENTER input setup.
and
buttons, select: 4-20 (4-20mA), 0-20
.
P
P
to
Copyright © 2011