Areas Of Application; Refrigerants; Oil Charge; Limits Of Application - Danfoss BOCK HG22e Operating Manual

Table of Contents

Advertisement

3| Areas of application

3.1 Refrigerants

• HFKW / HFC:
• (H)FCKW / (H)CFC:

3.2 Oil charge

The compressors are filled at the factory with the following oil type:
- for R134a, R404A/R507, R407C
- for R22
Compressors with ester oil charge ( BOCK lub E55 ) are marked with an X in the type
designation (e.g. HGX34e/380-4).
ATTENTION The oil level must be in the
D
GB

3.3 Limits of application

F
ATTENTION Compressor operation is possible within the operating limits.
E
I
Ru
8 | AQ451923867809en-000301
R134a, R404A/R507, R407C
R22
INFO
For refilling, we recommend the above oil types: see chapter 7.4
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
These can be found in Bock Compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140°C.
- Max. permissible switching frequency 8x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with supplementary cooling:
- Use only oils with high thermal stability.
- Avoid continuous operation near the threshold.
For operation with capacity regulator:
- Continuous operation, when the capacity regulator is activated,
is not permissible and can cause damage to the compressor.
- The suction gas superheat temperature may need to be reduced
or set individually when operating near to the threshold.
- When the capacity regulator is activated, the gas velocity in the
system can not under certain circumstances ensure that suffi-
cient oil is transported back to the compressor.
For operation with frequency converter:
- The maximum current and power consumption must not be
exceeded. In the case of operation above the mains frequency, the
application limit can therefore be limited.
(For more on the subject of frequency converters, see chapter
5.8, p. 18)
BOCK lub E55
BOCK lub A46
max.
oil level
min.
© Danfoss | Climate Solutions | 2024.07
HG22e =
0,7 Ltr.
HG34e =
0,8 Ltr.
Fig. 4